Skip to content
VoltCalcElectrical Calculators & Tools

Electrical Load Calculator

Calculate residential & commercial demand load under NEC 2026 Article 120 (with Section 120.7 PCS & Table 120.54 dryer demand), NEC 2023 Article 220, or IEC 60364 simultaneity (ks) & 3-phase L1/L2/L3 neutral unbalance.

Calculated Dwelling Service Demand (NEC 2026 Article 120)
35.8 kVA
Verify dwelling load calculations against NEC 2026 Article 120, dryer demand against Table 120.54, and dynamic EV/load management against Section 120.7 PCS.
First 10 kVA @ 100% + Remainder @ 40% + HVAC + EVSE [NEC 2026 Art. 120 / 2023 Art. 220]
How we got here

Step-by-step calculation

  1. Active Context: NFPA 70 (NEC 2026) | Dwelling Service 240 V (1-Phase)
  2. General Lighting & Receptacles = 2000 ft² × 3 VA/ft² = 6,000 VA
  3. Small-Appliance (2 × 1,500 VA = 3,000 VA) + Laundry (1,500 VA)
  4. Appliances Pool (Dryer per Table 120.54 = 5,000 VA, Range = 8,000 VA, Fixed = 12,000 VA) → General Pool = 35,500 VA
  5. Demand Factor (First 10,000 VA @ 100% + 25,500 VA @ 40%) = 20,200 VA
  6. HVAC Load = 6,000 VA | EVSE Load Included = 9,600 VA
  7. Total Demand = 35.80 kVA ÷ 240 V = 149.2 A → Recommended 150 A Service
Service Demand Current149.2 A
Recommended Service Size150 A
General Lighting + Appl. Pool35.50 kVA
Standard Method Lighting Demand5.63 kVA

Formula

NEC Art. 120/220: 10 kVA @ 100% + Rem @ 40% | IEC: P_dem = P_conn × k_s

Input definitions

SymbolInputUnitMeaning & code relevance
ModeLoad Calculation Method—Engineering input parameter for load calculation method, evaluated in real-time by the solver.
VSystem VoltageVNominal RMS AC or steady-state DC system potential (e.g., 120V/240V/480V NEC or 230V/400V IEC 60038).
AreaDwelling Floor Area (NEC 3 VA/ft² or 33 VA/m²)ft² / m²Engineering input parameter for dwelling floor area (nec 3 va/ft² or 33 va/m²) measured in ft² / m², evaluated in real-time by the solver.
UnitFloor Area Unit—Engineering input parameter for floor area unit, evaluated in real-time by the solver.
N_sa20A Small-Appliance Branch Circuits (min 2 @ 1500 VA)cktsEngineering input parameter for 20a small-appliance branch circuits (min 2 @ 1500 va) measured in ckts, evaluated in real-time by the solver.
N_laLaundry Branch Circuits (@ 1500 VA)cktsEngineering input parameter for laundry branch circuits (@ 1500 va) measured in ckts, evaluated in real-time by the solver.
VA_fixFastened-in-Place Appliances (Water Heater, Range, Dishwasher)VAEngineering input parameter for fastened-in-place appliances (water heater, range, dishwasher) measured in VA, evaluated in real-time by the solver.
VA_dryElectric Clothes Dryer Nameplate (NEC Table 120.54 min 5000 VA)VAEngineering input parameter for electric clothes dryer nameplate (nec table 120.54 min 5000 va) measured in VA, evaluated in real-time by the solver.
VA_hvacLargest HVAC / Heat Pump / Space Heating Load (100%)VAEngineering input parameter for largest hvac / heat pump / space heating load (100%) measured in VA, evaluated in real-time by the solver.
VA_evEV Charger / EVSE Load (Optional)VAEngineering input parameter for ev charger / evse load (optional) measured in VA, evaluated in real-time by the solver.
I_PCSNEC 2026 Sec. 120.7 Power Control System (PCS) Limit (Optional)AActive electrical or mechanical power transfer (A) dissipated or delivered to the load.
WConnected Load (for IEC / Quick Mode)WEngineering input parameter for connected load (for iec / quick mode) measured in W, evaluated in real-time by the solver.
DFDemand / Simultaneity Factor ks (for IEC / Quick Mode)%Engineering input parameter for demand / simultaneity factor ks (for iec / quick mode) measured in %, evaluated in real-time by the solver.
I_L1IEC 3-Phase L1 Current (Optional Unbalance Check)ASteady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.
I_L2IEC 3-Phase L2 Current (Optional Unbalance Check)ASteady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.
I_L3IEC 3-Phase L3 Current (Optional Unbalance Check)ASteady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.

Worked example

Subpanel Demand Load

12,000 W connected load with 80% diversity demand factor at 240 V.

  1. Demand Load = 12000 × 0.80 = 9600 W
  2. Demand Current = 9600 ÷ 240 = 40 A
  3. 125% Breaker = 50 A
Result: 9600 W (40 A)

Assumptions

  • Connected load is the sum of nameplate wattage ratings fed by the circuit or panel.
  • The user-entered demand factor represents the simultaneous diversity allowed by the applicable code.
  • Single-phase/split-phase current is calculated as Demand Watts ÷ System Voltage.

Limitations

  • A single overall demand factor is a quick planning estimate; formal NEC Article 220 residential/commercial service calculations apply tiered demand tables by appliance category.
  • Largest motor 125% rule and non-coincident HVAC/heating rules must be checked separately for service entrance permitting.

How it works

Applies diversity/demand factors to total connected appliance ratings to estimate realistic panel current and supply breaker sizing.

When to use it

  • Performing a residential dwelling or commercial service/feeder demand load calculation under NEC Article 120/220 or IEC 60364 diversity factor (k_s) rules.
  • Determining whether an existing 100 A or 200 A main service panel has sufficient spare capacity to add an EV charger, heat pump, or hot tub.
  • Calculating three-phase unbalanced phase currents and neutral conductor current in 4-wire wye/star distribution panels.

Practical real-world applications

  • Dwelling Service Upgrade Check: Evaluating a 2,400 sq ft home with an electric range, dryer, HVAC heat pump, and 48 A EV charger to determine if a 200 A service or Power Control System (NEC 120.7 PCS) is required.
  • Subpanel Feeder Sizing: Applying general lighting, small-appliance, and appliance demand factors to size a detached workshop or ADU subpanel feeder.
  • Three-Phase Panel Balancing: Computing maximum phase leg amperage and vector neutral current across L1, L2, and L3 in a 230/400 V or 120/208 V board.

Original Editorial Review & Technical Evaluation

Reviewed by VoltCalc Engineering Editorial

Computes total connected and demand electrical load using NEC 2023/2026 Article 120/220 Optional Feeder rules or IEC 60364 / BS 7671 simultaneity factors (k_s).

Intended Users

Master electricians sizing residential 100A–400A service entrances, solar/EV retrofit contractors checking main panel headroom, and MEP load analysts.

Key Engineering Features
  • Dual-code engine switching between NEC Optional Calculation (10 kVA @ 100% + 40% remainder + HVAC/EV) and IEC P_dem = P_conn × k_s
  • Evaluates NEC 2026 Article 120 Section 120.7 Power Control Systems (PCS) dynamic EVSE load-management impact
  • Recommends minimum service ampacity and main breaker rating against standard North American and IEC frames

Accuracy & methodology: Applies standard dwelling/branch demand multipliers as planning defaults while allowing engineering overrides for HVAC, electric heating, ranges, dryers, and EV chargers. Local utility diversity rules and commercial non-dwelling demand tables vary by occupancy and must be checked explicitly. Computational standards →

What to verify independently: Submit formal load calculations compliant with NFPA 70 (NEC 2023 Art. 220 / NEC 2026 Art. 120) or BS 7671 / IEC 60364-1 to your Authority Having Jurisdiction (AHJ).

Standards referenced:NFPA 70 (NEC 2026 Art. 120)NEC 2023 Art. 220IEC 60364-1 / BS 7671

Put the numbers to work with the Power Calculator, VA Calculator and Wire Size Calculator (Dual-Criteria Solver). For the background behind the numbers, read 100 Amp Wire Size: What Gauge You Actually Need and 200 Amp Wire Size: Gauge, Cable and Breaker.

Common mistakes

  • Simply summing 100% of every circuit breaker handle rating in a panelboard instead of applying code demand/diversity factors to actual connected VA loads.
  • Applying residential dwelling diversity/demand reductions to continuous EV charger loads (which must be taken at 125% continuous or managed by a listed EMS/PCS).
  • Subtracting minimum phase current from maximum phase current on a 3-phase 4-wire panel instead of using the 120° vector neutral current equation.

Safety & code notice

Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.

Frequently asked questions

Related Calculators

Related Unit Converters

Related Engineering Guides

Recommended Clamp Meters & Diagnostic Tools for Power & Load Verification

Affiliate links — helps keep VoltCalc free

Measure per-phase feeder current and line voltage with a CAT III/IV True-RMS clamp meter and trace branch circuit breakers before balancing panelboard loads.

Klein Tools CL800 Digital Clamp Meter
Klein ToolsGlobal (CAT IV 600V IEC 61010)

Klein Tools CL800 Digital Clamp Meter

Wide-jaw auto-ranging clamp meter with inrush capture for motor and compressor starting currents.

Type: Auto-ranging true-RMS clamp meterSafety rating: CAT III 600 V / CAT IV 300 VSpecial function: Inrush current capture
  • Inrush current capture — see the starting surge that trips breakers, not just the running current.
  • Wide jaw opening — accepts larger conductors and bundled cables that slim clamps cannot.
  • Auto-ranging true-RMS measurement — fast readings you can trust on non-linear loads.
Check Current Price
Fluke 325 True-RMS Clamp Meter
FlukeGlobal (CAT III 600V / CAT IV 300V IEC 61010)

Fluke 325 True-RMS Clamp Meter

Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.

Type: True-RMS clamp meterCurrent: AC and DCSafety rating: CAT III 600 V
  • AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
  • Clamp-on measurement — read current without disconnecting or disturbing the circuit.
  • Slim jaw profile — slides into crowded panels where bulky clamps will not fit.
Check Current Price
Siemens Q2100 100-Amp Double-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q2100 100-Amp Double-Pole Circuit Breaker

A 100-amp two-pole breaker for feeding a subpanel or a very large 240 V load.

Poles: 2 (double pole, common trip)Amperage: 100 AVoltage: 120/240 V AC
  • 100 amps per pole at 120/240 V — sized for subpanel feeders and very large 240 V loads.
  • Common trip — both poles open together, as a feeder protection device must.
  • Accepts 1 AWG through 4/0 conductors, torqued to 35 or 50 lb-in depending on the conductor size.
Check Current Price
Klein Tools ET310 Circuit Breaker Finder Kit
Klein ToolsNorth America (120V AC NEMA 5-15 GFCI)

Klein Tools ET310 Circuit Breaker Finder Kit

Finds the breaker feeding a circuit without shutting the panel down — the transmitter plugs into the outlet, the receiver traces it back.

Type: Circuit breaker finder kitIncluded: Receiver, transmitter, light socket adapter, ground adapter, carry caseWiring checks: Open ground, open neutral, open hot, hot/neutral reverse, hot/ground reverse
  • Transmitter and receiver pair — plug the transmitter into the socket, then sweep the receiver across the panel to identify the matching breaker.
  • Wiring status indicator on the transmitter — the same open ground, open neutral, open hot, reversed hot/neutral and reversed hot/ground checks as a standard outlet tester.
  • GFCI test button — trips a GFCI device to confirm it is actually protecting the circuit, not just installed.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →