Methodology, Assumptions & Safety
Exactly what each calculator does with your numbers — the formulas, the units, the rounding, and the factors it leaves out.
What VoltCalc is
VoltCalc is a free, no-signup electrical calculation platform for real-world electrical, solar, battery, wiring and energy calculations. Its purpose is to help you get a number quickly, understand how that number was produced, and know when it needs checking by someone qualified.
Every calculator runs entirely in your browser. Nothing you type is sent to a server or stored, and no account is required.
Formulas used
Calculations follow standard electrical engineering relationships. No proprietary correction factors and no hidden multipliers are applied.
| Area | Relationship |
|---|---|
| Ohm’s law & power | V = I × R · I = V ÷ R · R = V ÷ I · P = V × I · P = I² × R · P = V² ÷ R |
| Apparent power (VA) | VA = V × I (single-phase) · kVA = √3 × V × I ÷ 1000 (three-phase) |
| Voltage drop | V_drop = 2 × I × L × R ÷ 1000 (single-phase) · V_drop = 1.732 × I × L × R ÷ 1000 (three-phase) |
| Energy & cost | E (kWh) = P (W) × t (h) ÷ 1000 · Cost = kWh × tariff |
| Battery runtime | Hours = (Ah × system V × DoD × η) ÷ load W |
| Solar array | Daily Wh = array W × peak sun hours × derate factor |
Units
Inputs use SI base units unless a unit is named beside the field: volts (V), amperes (A), ohms (Ω), watts (W), watt-hours (Wh), kilowatt-hours (kWh), metres (m) or feet (ft). Milliamps and kilo-ohms are not converted automatically — enter 0.25 A rather than 250 mA.
Rounding
Calculations are carried out at full floating-point precision and only rounded for display, normally to three or four significant figures. Results are planning estimates, not measured values: they inherit the accuracy of what you entered, so a current estimate based on nameplate figures is not the same as a clamp-meter reading.
Conductor resistance and temperature
Resistance values are the standard annealed-copper and aluminium figures at 20 °C stated above. Where a conductor temperature is provided, resistance is adjusted upwards for the temperature rise, because a warm conductor has more resistance and therefore more voltage drop. The calculators do not re-derive resistance from insulation type, conductor class or stranding — those vary by product and are published by the manufacturer.
Voltage systems supported
Single-phase and balanced three-phase circuits, at any system voltage you enter — 120 V, 230 V, 240 V, 400 V, 480 V and DC systems alike. The phase selector changes the multiplier, nothing else.
Assumptions
- Circuits are treated as resistive unless a power factor is entered. Motors, transformers and other inductive loads need the power factor and efficiency fields filled in.
- Conductor resistance is taken at 20 °C unless a conductor temperature is supplied. Copper is 0.0175 Ω·mm²/m and aluminium 0.0282 Ω·mm²/m at that temperature.
- Resistance is adjusted for temperature using a coefficient of 0.00393 per °C for copper, so a hot conductor is treated as having more resistance and therefore more drop.
- Voltage drop is calculated from the one-way length you enter. The calculator doubles it for the out-and-back path on single-phase circuits and applies the √3 factor for three-phase circuits, and it states this on the result.
- Balanced loads are assumed for three-phase work. Unbalanced or single-phase-to-neutral loads need to be assessed phase by phase.
- Battery figures are planning values: depth of discharge and efficiency come from the inputs, not from a battery datasheet.
What the calculators do not account for
- Code ampacity tables, derating for grouping, ambient temperature, or installation method.
- Harmonics, DC offset, or non-linear loads.
- Motor starting current, inrush, or protective-device trip curves.
- Shading, soiling, orientation and seasonal variation in solar estimates.
- Battery ageing, internal resistance, or temperature effects on capacity.
- Taxes, standing charges, or time-of-use tariffs beyond the single rate you enter.
A voltage drop result tells you what the drop is for the conductor you chose. It does not tell you that the conductor is adequate — that depends on the tables in the code that applies where you are, and on the installation conditions on site.
Why you must verify against local codes
Voltage-drop limits, allowable current-carrying capacities, protective-device selection and earthing requirements all vary by jurisdiction and by the edition of the code in force. Common planning references — such as 3% on a branch circuit and 5% overall — are guidance, not universal legal limits.
Status of the tool
VoltCalc is an educational and planning tool. It is not a design authority, a compliance check, or a replacement for licensed engineering or installation work. Final designs should be verified against applicable local codes, standards, manufacturer instructions and a qualified professional.