Exactly what each calculator does with your numbers — the formulas, the units, the rounding, and the factors it leaves out.

What VoltCalc is

VoltCalc is a free, no-signup electrical calculation platform for real-world electrical, solar, battery, wiring and energy calculations. Its purpose is to help you get a number quickly, understand how that number was produced, and know when it needs checking by someone qualified.

Every calculator runs entirely in your browser. Nothing you type is sent to a server or stored, and no account is required.

Formulas used

Calculations follow standard electrical engineering relationships. No proprietary correction factors and no hidden multipliers are applied.

AreaRelationship
Ohm’s law & powerV = I × R · I = V ÷ R · R = V ÷ I · P = V × I · P = I² × R · P = V² ÷ R
Apparent power (VA)VA = V × I (single-phase) · kVA = √3 × V × I ÷ 1000 (three-phase)
Voltage dropV_drop = 2 × I × L × R ÷ 1000 (single-phase) · V_drop = 1.732 × I × L × R ÷ 1000 (three-phase)
Energy & costE (kWh) = P (W) × t (h) ÷ 1000 · Cost = kWh × tariff
Battery runtimeHours = (Ah × system V × DoD × η) ÷ load W
Solar arrayDaily Wh = array W × peak sun hours × derate factor

Units

Inputs use SI base units unless a unit is named beside the field: volts (V), amperes (A), ohms (Ω), watts (W), watt-hours (Wh), kilowatt-hours (kWh), metres (m) or feet (ft). Milliamps and kilo-ohms are not converted automatically — enter 0.25 A rather than 250 mA.

Rounding

Calculations are carried out at full floating-point precision and only rounded for display, normally to three or four significant figures. Results are planning estimates, not measured values: they inherit the accuracy of what you entered, so a current estimate based on nameplate figures is not the same as a clamp-meter reading.

Conductor resistance and temperature

Resistance values are the standard annealed-copper and aluminium figures at 20 °C stated above. Where a conductor temperature is provided, resistance is adjusted upwards for the temperature rise, because a warm conductor has more resistance and therefore more voltage drop. The calculators do not re-derive resistance from insulation type, conductor class or stranding — those vary by product and are published by the manufacturer.

Voltage systems supported

Single-phase and balanced three-phase circuits, at any system voltage you enter — 120 V, 230 V, 240 V, 400 V, 480 V and DC systems alike. The phase selector changes the multiplier, nothing else.

Assumptions

  • Circuits are treated as resistive unless a power factor is entered. Motors, transformers and other inductive loads need the power factor and efficiency fields filled in.
  • Conductor resistance is taken at 20 °C unless a conductor temperature is supplied. Copper is 0.0175 Ω·mm²/m and aluminium 0.0282 Ω·mm²/m at that temperature.
  • Resistance is adjusted for temperature using a coefficient of 0.00393 per °C for copper, so a hot conductor is treated as having more resistance and therefore more drop.
  • Voltage drop is calculated from the one-way length you enter. The calculator doubles it for the out-and-back path on single-phase circuits and applies the √3 factor for three-phase circuits, and it states this on the result.
  • Balanced loads are assumed for three-phase work. Unbalanced or single-phase-to-neutral loads need to be assessed phase by phase.
  • Battery figures are planning values: depth of discharge and efficiency come from the inputs, not from a battery datasheet.

What the calculators do not account for

  • Code ampacity tables, derating for grouping, ambient temperature, or installation method.
  • Harmonics, DC offset, or non-linear loads.
  • Motor starting current, inrush, or protective-device trip curves.
  • Shading, soiling, orientation and seasonal variation in solar estimates.
  • Battery ageing, internal resistance, or temperature effects on capacity.
  • Taxes, standing charges, or time-of-use tariffs beyond the single rate you enter.

A voltage drop result tells you what the drop is for the conductor you chose. It does not tell you that the conductor is adequate — that depends on the tables in the code that applies where you are, and on the installation conditions on site.

Why you must verify against local codes

Voltage-drop limits, allowable current-carrying capacities, protective-device selection and earthing requirements all vary by jurisdiction and by the edition of the code in force. Common planning references — such as 3% on a branch circuit and 5% overall — are guidance, not universal legal limits.

Status of the tool

VoltCalc is an educational and planning tool. It is not a design authority, a compliance check, or a replacement for licensed engineering or installation work. Final designs should be verified against applicable local codes, standards, manufacturer instructions and a qualified professional.