Skip to content

Electrical Reference

The formulas, symbols and units behind the calculations — kept in one place.

Fundamentals

Reference Pages

Charts

Charts & Tools

Reference data alongside interactive tools.

Formulas

Common Electrical Formulas

Ohm's Law, power, AC, motors, transformers, batteries and wiring — the relationships you reach for most often, in one table.

Full formula reference
QuantityFormula
Ohm's Law & Power
VoltageV = I × R
CurrentI = V ÷ R
ResistanceR = V ÷ I
Real PowerP = V × I
Power from I and RP = I² × R
Power from V and RP = V² ÷ R
EnergyE = P × t
AC Power
Apparent PowerS = V × I
Real PowerP = V × I × PF
Reactive PowerQ = √(S² − P²)
Power FactorPF = P ÷ S = cos φ
Three-Phase PowerP = √3 × V_L × I × PF
ImpedanceZ = √(R² + X²)
Inductive ReactanceX_L = 2πfL
Capacitive ReactanceX_C = 1 ÷ (2πfC)
Motors
Three-Phase Motor CurrentI = P ÷ (√3 × V × PF × η)
Single-Phase Motor CurrentI = P ÷ (V × PF × η)
Motor Output PowerP_out = √3 × V × I × PF × η
Efficiencyη = P_out ÷ P_in
Synchronous SpeedN = 120f ÷ P
Transformers
Turns RatioN_p ÷ N_s = V_p ÷ V_s
Primary CurrentI_p = S ÷ V_p
Secondary CurrentI_s = S ÷ V_s
Three-Phase CurrentI = S ÷ (√3 × V)
Batteries & Solar
Battery EnergyWh = Ah × V
Runtimet = (Ah × V × DoD × η) ÷ Load
Required CapacityAh = (Load × t) ÷ (V × DoD × η)
Solar ArrayN = E ÷ (Panel W × Sun Hours × Derate)
Wiring
Voltage Drop (Single Phase)V_d = 2 × I × L × ρ ÷ A
Voltage Drop (Three Phase)V_d = √3 × I × L × ρ ÷ A
Conductor ResistanceR = ρ × L ÷ A
Joule HeatingQ = I² × R × t

Formulas are given for steady-state conditions. For AC work include power factor and use impedance in place of resistance where the load is reactive.