Wire Gauge & Metric Size Chart (AWG / mm²)
Side-by-side North American (AWG / kcmil from 1000 kcmil and 4/0 AWG down to 30 AWG) and International IEC 60228 (1.5 mm² to 300 mm²) conductor reference tables with cross-sectional area, bare diameter, 20 °C DC resistance, and planning ampacity.
North American AWG & kcmil Conductor Chart (1000 kcmil & 4/0 AWG down to 30 AWG)
ASTM B258 geometric cross-sectional area, bare solid diameter, 20 °C DC resistance (Ω/1000 ft & Ω/km), next larger IEC 60228 metric size, and non-normative 75 °C planning ampacities (verify against NFPA 70 Table 310.16 & Chapter 9 Table 8).
| Wire Size | Area (mm²) | Area (cmil / kcmil) | Diameter (mm / in) | Next IEC (mm²) | Cu R₂₀ (Ω/kft | Ω/km) | Al R₂₀ (Ω/kft) | Cu 75°C Ampacity* | Al 75°C Ampacity* |
|---|---|---|---|---|---|---|---|---|
| 30 AWG | 0.051 mm² | 101 cmil (0.10 kcmil) | 0.255 mm (0.0100 in) | 1.5 mm² | 103.2 Ω/kft | 338.5 Ω/km | 168.8 Ω/kft | Control / Signal | — |
| 28 AWG | 0.081 mm² | 160 cmil (0.16 kcmil) | 0.321 mm (0.0126 in) | 1.5 mm² | 64.89 Ω/kft | 212.9 Ω/km | 106.2 Ω/kft | Control / Signal | — |
| 26 AWG | 0.129 mm² | 254 cmil (0.25 kcmil) | 0.405 mm (0.0159 in) | 1.5 mm² | 40.81 Ω/kft | 133.9 Ω/km | 66.75 Ω/kft | Control / Signal | — |
| 24 AWG | 0.205 mm² | 404 cmil (0.40 kcmil) | 0.511 mm (0.0201 in) | 1.5 mm² | 25.67 Ω/kft | 84.21 Ω/km | 41.97 Ω/kft | Control / Signal | — |
| 22 AWG | 0.326 mm² | 642 cmil (0.64 kcmil) | 0.644 mm (0.0253 in) | 1.5 mm² | 16.14 Ω/kft | 52.96 Ω/km | 26.4 Ω/kft | Control / Signal | — |
| 20 AWG | 0.518 mm² | 1,022 cmil (1.02 kcmil) | 0.812 mm (0.0320 in) | 1.5 mm² | 10.15 Ω/kft | 33.31 Ω/km | 16.61 Ω/kft | Control / Signal | — |
| 18 AWG | 0.823 mm² | 1,624 cmil (1.62 kcmil) | 1.024 mm (0.0403 in) | 1.5 mm² | 6.386 Ω/kft | 20.95 Ω/km | 10.44 Ω/kft | Control / Signal | — |
| 16 AWG | 1.309 mm² | 2,583 cmil (2.58 kcmil) | 1.291 mm (0.0508 in) | 1.5 mm² | 4.014 Ω/kft | 13.17 Ω/km | 6.568 Ω/kft | Control / Signal | — |
| 14 AWG | 2.081 mm² | 4,107 cmil (4.11 kcmil) | 1.628 mm (0.0641 in) | 2.5 mm² | 2.525 Ω/kft | 8.285 Ω/km | 4.13 Ω/kft | 20 A | — |
| 12 AWG | 3.309 mm² | 6,530 cmil (6.53 kcmil) | 2.053 mm (0.0808 in) | 4 mm² | 1.588 Ω/kft | 5.211 Ω/km | 2.598 Ω/kft | 25 A | 20 A |
| 10 AWG | 5.261 mm² | 10,383 cmil (10.38 kcmil) | 2.588 mm (0.1019 in) | 6 mm² | 0.9988 Ω/kft | 3.277 Ω/km | 1.634 Ω/kft | 35 A | 30 A |
| 8 AWG | 8.366 mm² | 16,510 cmil (16.51 kcmil) | 3.264 mm (0.1285 in) | 10 mm² | 0.6282 Ω/kft | 2.061 Ω/km | 1.027 Ω/kft | 50 A | 40 A |
| 6 AWG | 13.300 mm² | 26,251 cmil (26.25 kcmil) | 4.115 mm (0.1620 in) | 16 mm² | 0.395 Ω/kft | 1.296 Ω/km | 0.6462 Ω/kft | 65 A | 50 A |
| 4 AWG | 21.150 mm² | 41,741 cmil (41.74 kcmil) | 5.189 mm (0.2043 in) | 25 mm² | 0.2485 Ω/kft | 0.8152 Ω/km | 0.4063 Ω/kft | 85 A | 65 A |
| 3 AWG | 26.670 mm² | 52,635 cmil (52.63 kcmil) | 5.827 mm (0.2294 in) | 35 mm² | 0.197 Ω/kft | 0.6464 Ω/km | 0.3222 Ω/kft | 100 A | 75 A |
| 2 AWG | 33.630 mm² | 66,371 cmil (66.37 kcmil) | 6.544 mm (0.2576 in) | 35 mm² | 0.1563 Ω/kft | 0.5127 Ω/km | 0.2556 Ω/kft | 115 A | 90 A |
| 1 AWG | 42.410 mm² | 83,693 cmil (83.69 kcmil) | 7.348 mm (0.2893 in) | 50 mm² | 0.1239 Ω/kft | 0.4066 Ω/km | 0.2027 Ω/kft | 130 A | 100 A |
| 1/0 AWG | 53.480 mm² | 105,535 cmil (105.50 kcmil) | 8.251 mm (0.3249 in) | 70 mm² | 0.09827 Ω/kft | 0.3224 Ω/km | 0.1607 Ω/kft | 150 A | 120 A |
| 2/0 AWG | 67.430 mm² | 133,077 cmil (133.10 kcmil) | 9.266 mm (0.3648 in) | 70 mm² | 0.07794 Ω/kft | 0.2557 Ω/km | 0.1275 Ω/kft | 175 A | 135 A |
| 3/0 AWG | 85.030 mm² | 167,806 cmil (167.80 kcmil) | 10.405 mm (0.4096 in) | 95 mm² | 0.06181 Ω/kft | 0.2028 Ω/km | 0.1011 Ω/kft | 200 A | 155 A |
| 4/0 AWG | 107.200 mm² | 211,600 cmil (211.60 kcmil) | 11.684 mm (0.4600 in) | 120 mm² | 0.04901 Ω/kft | 0.1608 Ω/km | 0.08016 Ω/kft | 230 A | 180 A |
| 250 kcmil | 126.700 mm² | 250,000 cmil (250.00 kcmil) | 12.700 mm (0.5000 in) | 150 mm² | 0.04148 Ω/kft | 0.1361 Ω/km | 0.06785 Ω/kft | 255 A | 205 A |
| 300 kcmil | 152.000 mm² | 300,000 cmil (300.00 kcmil) | 13.912 mm (0.5477 in) | 185 mm² | 0.03456 Ω/kft | 0.1134 Ω/km | 0.05654 Ω/kft | 285 A | 230 A |
| 350 kcmil | 177.300 mm² | 350,000 cmil (350.00 kcmil) | 15.027 mm (0.5916 in) | 185 mm² | 0.02963 Ω/kft | 0.09722 Ω/km | 0.04846 Ω/kft | 310 A | 250 A |
| 400 kcmil | 202.700 mm² | 400,000 cmil (400.00 kcmil) | 16.064 mm (0.6325 in) | 240 mm² | 0.02593 Ω/kft | 0.08506 Ω/km | 0.0424 Ω/kft | 335 A | 270 A |
| 500 kcmil | 253.400 mm² | 500,000 cmil (500.00 kcmil) | 17.961 mm (0.7071 in) | 300 mm² | 0.02074 Ω/kft | 0.06805 Ω/km | 0.03392 Ω/kft | 380 A | 310 A |
| 600 kcmil | 304.000 mm² | 600,000 cmil (600.00 kcmil) | 19.675 mm (0.7746 in) | 300 mm² | 0.01729 Ω/kft | 0.05671 Ω/km | 0.02827 Ω/kft | Control / Signal | — |
| 750 kcmil | 380.000 mm² | 750,000 cmil (750.00 kcmil) | 21.997 mm (0.8660 in) | 300 mm² | 0.01383 Ω/kft | 0.04537 Ω/km | 0.02262 Ω/kft | Control / Signal | — |
| 1000 kcmil | 506.700 mm² | 1,000,000 cmil (1000.00 kcmil) | 25.400 mm (1.0000 in) | 300 mm² | 0.01037 Ω/kft | 0.03403 Ω/km | 0.01696 Ω/kft | Control / Signal | — |
IEC 60228 Metric Conductor Reference Chart (1.5 mm² to 300 mm²)
International metric nominal cross-sectional areas from 1.5 mm² to 300 mm² with maximum 20 °C DC conductor resistance R₂₀ (Ω/km & Ω/1000 ft), safe upsized AWG/kcmil equivalents, and non-normative planning ampacity defaults (verify against IEC 60364-5-52 Method C / BS 7671 Appendix 4).
| IEC Size (mm²) | Solid Ø (mm) | Cu R₂₀ (Ω/km) | Cu R₂₀ (Ω/1000 ft) | Al R₂₀ (Ω/km) | Closest AWG | Safe Upsized AWG/kcmil | Cu 70°C PVC (Iz)* | Cu 90°C XLPE (Iz)* |
|---|---|---|---|---|---|---|---|---|
| 1.5 mm² | 1.38 mm | 12.1 Ω/km | 3.6881 Ω/kft | 18.1 Ω/km | 16 AWG | 14 AWG | 19.5 A | 24 A |
| 2.5 mm² | 1.78 mm | 7.41 Ω/km | 2.2586 Ω/kft | 12.1 Ω/km | 14 AWG | 12 AWG | 27 A | 33 A |
| 4 mm² | 2.26 mm | 4.61 Ω/km | 1.4051 Ω/kft | 7.41 Ω/km | 12 AWG | 10 AWG | 36 A | 45 A |
| 6 mm² | 2.76 mm | 3.08 Ω/km | 0.9388 Ω/kft | 4.61 Ω/km | 10 AWG | 8 AWG | 46 A | 58 A |
| 10 mm² | 3.57 mm | 1.83 Ω/km | 0.5578 Ω/kft | 3.08 Ω/km | 8 AWG | 6 AWG | 63 A | 80 A |
| 16 mm² | 4.51 mm | 1.15 Ω/km | 0.3505 Ω/kft | 1.91 Ω/km | 6 AWG | 4 AWG | 85 A | 107 A |
| 25 mm² | 5.64 mm | 0.727 Ω/km | 0.2216 Ω/kft | 1.2 Ω/km | 3 AWG | 3 AWG | 112 A | 138 A |
| 35 mm² | 6.68 mm | 0.524 Ω/km | 0.1597 Ω/kft | 0.868 Ω/km | 2 AWG | 1 AWG | 138 A | 169 A |
| 50 mm² | 7.98 mm | 0.387 Ω/km | 0.118 Ω/kft | 0.641 Ω/km | 1/0 AWG | 1/0 AWG | 168 A | 207 A |
| 70 mm² | 9.44 mm | 0.268 Ω/km | 0.0817 Ω/kft | 0.443 Ω/km | 2/0 AWG | 3/0 AWG | 213 A | 268 A |
| 95 mm² | 11.00 mm | 0.193 Ω/km | 0.0588 Ω/kft | 0.32 Ω/km | 3/0 AWG | 4/0 AWG | 258 A | 328 A |
| 120 mm² | 12.36 mm | 0.153 Ω/km | 0.0466 Ω/kft | 0.253 Ω/km | 250 kcmil | 250 kcmil | 299 A | 382 A |
| 150 mm² | 13.82 mm | 0.124 Ω/km | 0.0378 Ω/kft | 0.206 Ω/km | 300 kcmil | 300 kcmil | 344 A | 441 A |
| 185 mm² | 15.35 mm | 0.0991 Ω/km | 0.0302 Ω/kft | 0.164 Ω/km | 350 kcmil | 400 kcmil | 392 A | 506 A |
| 240 mm² | 17.48 mm | 0.0754 Ω/km | 0.023 Ω/kft | 0.125 Ω/km | 500 kcmil | 500 kcmil | 461 A | 599 A |
| 300 mm² | 19.54 mm | 0.0601 Ω/km | 0.0183 Ω/kft | 0.1 Ω/km | 600 kcmil | 600 kcmil | 530 A | 693 A |
How it works
North American installations size conductors using the logarithmic ASTM B258 American Wire Gauge (AWG) scale and thousands of circular mils (kcmil), whereas IEC 60364 / BS 7671 installations use IEC 60228 nominal metric cross-sectional areas (mm²) standardized by maximum 20 °C DC resistance (Ω/km).
When to use it
Use it when cross-referencing North American AWG/kcmil sizes with IEC 60228 metric (mm²) cable sizes, looking up 20 °C resistance in Ω/1000 ft or Ω/km, or checking baseline planning ampacity figures.
Common mistakes
Treating the 75°C or Method C ampacity column as unconditional—NEC 240.4(D) caps small branch conductors (14 AWG at 15 A, 12 AWG at 20 A, 10 AWG at 30 A), ambient temperature or conduit bundling requires derating, and metric vs. AWG lugs are not mechanically interchangeable without dual listing.
Related Calculators
Wire Size Calculator (Dual-Criteria Solver)
Size copper and aluminum conductors in AWG or mm² for ampacity and voltage drop.
Voltage Drop Calculator
Calculate AC and DC voltage drop across AWG or metric mm² copper and aluminum runs.
Circuit Breaker Size Calculator
Select circuit breaker and MCB ratings for continuous loads and cable ampacity.
Electrical Load Calculator
Calculate residential and commercial service demand loads and feeder current.
Related Unit Converters
AWG to mm² Converter (American Wire Gauge to Metric)
Convert American Wire Gauge (AWG) to metric mm² area, diameter, and resistance.
mm² to AWG Converter (Metric Cable to American Wire Gauge)
Convert metric conductor area in mm² to the nearest AWG size and DC resistance.
Conductor Area Converter (mm², cmil, kcmil, sq in, sq ft, m²)
Convert conductor areas between mm², circular mils, kcmil, sq inches, and cm².
Electrical Length Converter (Meters, Feet, Inches, Yards, km, Miles)
Convert cable lengths between meters, feet, inches, millimeters, yards, and miles.
Related Engineering Guides
How to Choose Cables & Wire
Select conductor sizes, insulation ratings, and cables for ampacity and drop limits.
100 Amp Wire Size: What Gauge You Actually Need
Select copper and aluminum conductor sizes in AWG and mm² for 100 A subpanel runs.
200 Amp Wire Size: Gauge, Cable and Breaker
Size copper and aluminum service and feeder cables in AWG and mm² for 200 A panels.
How to Choose Wire Strippers & Crimpers
Match precision wire strippers and ratcheting crimpers to solid and stranded wire.
Frequently Asked Questions
Related Equipment

Klein Tools 11063W Wire Stripper and Cutter
Self-adjusting stripper that grips, strips and cuts common building wire in one motion.
- Self-adjusting action — squeeze once and the tool sets itself to the conductor size, so strips are repeatable.
- Clean strip without nicking — protects the copper, which is what keeps a termination reliable long term.
- Built-in cutter and plier nose — you can cut, strip and twist without swapping tools.

Klein Tools 3005CR Ratcheting Crimper
Ratcheting crimper that locks until the crimp is complete, so every termination is fully formed.
- Ratcheting mechanism — the tool stays locked until the crimp is fully formed, so a weak grip cannot produce a weak joint.
- 22–10 AWG range — covers the terminal sizes used in most panel and control wiring.
- Insulated and non-insulated terminals — one tool handles both, so you are not carrying two.

Fluke 325 True-RMS Clamp Meter
Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.
- AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
- Clamp-on measurement — read current without disconnecting or disturbing the circuit.
- Slim jaw profile — slides into crowded panels where bulky clamps will not fit.

Siemens Q120 20-Amp Single-Pole Circuit Breaker
The standard 20-amp single-pole breaker for lighting, receptacles and small appliances on 120 V circuits.
- 20-amp single pole for 120 V circuits — sized for standard 12 AWG receptacle and lighting circuits.
- 10 kA interrupting rating — handles the fault current available in typical residential panels.
- SWD (switching duty) listed — approved for switching fluorescent lighting loads, not just overload protection.