100 Amp Wire Size: What Gauge You Actually Need

VoltCalc EditorialPublished 2026-11-05Updated 2026-11-167 min read

The short answer for 100 amps

For a 100 A circuit, the usual answer is 3 AWG copper or 1 AWG aluminium, read from the 75 °C ampacity column. The equipment grounding conductor is 8 AWG copper or 6 AWG aluminium.

In metric terms 3 AWG is about 26.7 mm², so 25 mm² is the nearest common size and 35 mm² is the next step up. Which of the two suits your job depends on the installation method and the derating factors behind it, not on the conversion alone.

Why there is no single number

Four things move the answer, and any of them can turn "3 AWG" into "2 AWG":

  • Termination temperature. A conductor's usable ampacity depends on the column you may read, which depends on the temperature rating of the terminals and the insulation. Equipment marked 75 °C means the 75 °C column.
  • Ambient temperature. A conductor in a hot roof space, plant room or engine bay carries less than the table value once the correction factor is applied.
  • Bundle count. More than three current-carrying conductors in one raceway means an adjustment factor, and the rating drops accordingly.
  • Voltage drop. On a long run, a conductor that passes the ampacity check can still lose too much voltage. Then the next size up becomes the answer.

Copper or aluminium

Aluminium needs roughly two AWG sizes larger than copper to carry the same current, which is why 1 AWG aluminium stands in for 3 AWG copper. Aluminium is lighter and cheaper at large sizes and is common for service and feeder work; it needs terminals listed for the material and the correct torque, and it is less forgiving of a loose connection. Copper is the default for branch circuits, short runs and equipment terminations.

100 A service versus 100 A subpanel

  • Subpanel feeder: typically 3 AWG copper or 1 AWG aluminium for the ungrounded conductors, 8 AWG copper for the equipment grounding conductor.
  • Neutral: it is a current-carrying conductor. Keep it the same size as the ungrounded conductors unless you have calculated that the unbalanced load allows a reduction.
  • Dwelling service: a 100 A service to a dwelling unit may use the reduced service-conductor allowance in NEC 310.12, which is more generous than the ampacity table alone. That allowance is for dwelling units — it does not cover a subpanel feeding a workshop or a garage.

When 3 AWG copper is not enough

Voltage drop is what catches people out on 100 A feeders. Take 100 A over 40 m of 3 AWG copper: the conductor works out at roughly 0.026 Ω, so a single-phase 240 V circuit loses about 5.3 V — around 2.2%. Stretch the same run to 60 m and the drop reaches about 3.3%, past the usual 3% branch-circuit target, and 2 AWG becomes the right call.

The arithmetic is one line — drop = 2 × current × length × resistivity ÷ area, with the 2 accounting for the current travelling out and back — and the voltage drop calculator runs it with your own length, voltage and conductor material.

Metric sizing in practice

For a 100 A circuit on IEC-style installation, 25 mm² copper is the common starting point for a short, freely ventilated run, and 35 mm² is the usual choice once the run is long, the cable is grouped with others, or it is buried or in a thermally insulated wall. The current-carrying figure moves a long way between clipped direct, in conduit and inside insulation, so read it from the table for the method you actually have.

The breaker must match the cable

A 100 A breaker protects a cable rated at least 100 A after derating. A 100 A breaker on a conductor that can carry only 85 A is a fire waiting for a load — and a 100 A breaker on a conductor rated 125 A is simply a missed opportunity to protect the circuit properly.

Verify before you install

Ampacity tables, derating factors and the dwelling-service allowance live in the electrical code that applies where you work — NEC 2023 in the United States, with earlier editions still in force in some jurisdictions, and BS 7671 or IEC 60364 elsewhere. Treat the figures here as the starting point for that check rather than a substitute for it, and have installation work verified by a qualified professional.

Side-by-Side Worked Examples: North America (NEC) vs. International (IEC 60364 / BS 7671)

North American (NEC 2023/2026) Worked Example

Sizing a 100 A, 120/240 V feeder to a detached workshop subpanel 120 ft (36.6 m) away vs. a North America-specific dwelling service.

  1. Feeder vs. dwelling service rule: NEC 310.12 (North America dwelling unit services only) allows 4 AWG Cu / 2 AWG Al for a 100 A residential main service, but a detached workshop subpanel is a feeder governed by NFPA 70 Table 310.16 and NEC 110.14(C) 75 °C terminals — requiring 3 AWG Cu (100 A) or 1 AWG Al (100 A) with an 8 AWG Cu EGC.
  2. Voltage drop check at 80 A continuous subpanel load on 3 AWG Cu (26.67 mm²): ΔV = 2 × 80 × (0.0175 × 36.6 ÷ 26.67) = 3.84 V (1.60%) — well within 3%; verify Table 310.15(B)(1)(1) if ambient exceeds 30 °C.

International (IEC 60364 / BS 7671) Worked Example

Sizing a 100 A, 230 V 1-phase (or 400 V 3-phase) sub-main routed 35 m clipped direct (Method C) in 35 °C ambient beside one circuit (C_a = 0.94, C_g = 0.80, non-normative planning defaults; verify against IEC 60364-5-52 / BS 7671 Appendix 4 Table 4Ab).

  1. Coordination (I_b ≤ I_n ≤ I_z): Required base rating ≥ 100 ÷ (0.94 × 0.80) = 133.0 A -> select 35 mm² XLPE copper (typical Method C ~147 A -> I_z = 110.5 A, satisfying I_b ≤ I_n (100 A) ≤ I_z (110.5 A); un-derated 25 mm² would fail once grouped).
  2. Voltage drop & adiabatic PE: At 100 A single-phase, ΔV = 2 × 100 × (0.0175 × 35 ÷ 35) = 3.50 V (1.52%). For a 3,200 A earth fault cleared in 0.1 s (k = 143), adiabatic PE S = √(3,200² × 0.1) ÷ 143 = 7.08 mm² -> 10 mm² or 16 mm² protective conductor.

Related Calculators

Related Unit Converters

Frequently Asked Questions

For a 100 A circuit on copper, 3 AWG read from the 75 °C ampacity column, or 1 AWG if the conductor is aluminium. The equipment grounding conductor is 8 AWG copper or 6 AWG aluminium. Confirm the column you are allowed to use from the termination ratings on your equipment.

Recommended Tools & Equipment for This Guide

Affiliate links — helps keep VoltCalc free
Siemens Q2100 100-Amp Double-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q2100 100-Amp Double-Pole Circuit Breaker

A 100-amp two-pole breaker for feeding a subpanel or a very large 240 V load.

Poles: 2 (double pole, common trip)Amperage: 100 AVoltage: 120/240 V AC
  • 100 amps per pole at 120/240 V — sized for subpanel feeders and very large 240 V loads.
  • Common trip — both poles open together, as a feeder protection device must.
  • Accepts 1 AWG through 4/0 conductors, torqued to 35 or 50 lb-in depending on the conductor size.
Check Current Price
Fluke 325 True-RMS Clamp Meter
FlukeGlobal (CAT III 600V / CAT IV 300V IEC 61010)

Fluke 325 True-RMS Clamp Meter

Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.

Type: True-RMS clamp meterCurrent: AC and DCSafety rating: CAT III 600 V
  • AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
  • Clamp-on measurement — read current without disconnecting or disturbing the circuit.
  • Slim jaw profile — slides into crowded panels where bulky clamps will not fit.
Check Current Price
Klein Tools CL800 Digital Clamp Meter
Klein ToolsGlobal (CAT IV 600V IEC 61010)

Klein Tools CL800 Digital Clamp Meter

Wide-jaw auto-ranging clamp meter with inrush capture for motor and compressor starting currents.

Type: Auto-ranging true-RMS clamp meterSafety rating: CAT III 600 V / CAT IV 300 VSpecial function: Inrush current capture
  • Inrush current capture — see the starting surge that trips breakers, not just the running current.
  • Wide jaw opening — accepts larger conductors and bundled cables that slim clamps cannot.
  • Auto-ranging true-RMS measurement — fast readings you can trust on non-linear loads.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →

Related Engineering Guides