100 Amp Wire Size: What Gauge You Actually Need
The short answer for 100 amps
For a 100 A circuit, the usual answer is 3 AWG copper or 1 AWG aluminium, read from the 75 °C ampacity column. The equipment grounding conductor is 8 AWG copper or 6 AWG aluminium.
In metric terms 3 AWG is about 26.7 mm², so 25 mm² is the nearest common size and 35 mm² is the next step up. Which of the two suits your job depends on the installation method and the derating factors behind it, not on the conversion alone.
Why there is no single number
Four things move the answer, and any of them can turn "3 AWG" into "2 AWG":
- Termination temperature. A conductor's usable ampacity depends on the column you may read, which depends on the temperature rating of the terminals and the insulation. Equipment marked 75 °C means the 75 °C column.
- Ambient temperature. A conductor in a hot roof space, plant room or engine bay carries less than the table value once the correction factor is applied.
- Bundle count. More than three current-carrying conductors in one raceway means an adjustment factor, and the rating drops accordingly.
- Voltage drop. On a long run, a conductor that passes the ampacity check can still lose too much voltage. Then the next size up becomes the answer.
Copper or aluminium
Aluminium needs roughly two AWG sizes larger than copper to carry the same current, which is why 1 AWG aluminium stands in for 3 AWG copper. Aluminium is lighter and cheaper at large sizes and is common for service and feeder work; it needs terminals listed for the material and the correct torque, and it is less forgiving of a loose connection. Copper is the default for branch circuits, short runs and equipment terminations.
100 A service versus 100 A subpanel
- Subpanel feeder: typically 3 AWG copper or 1 AWG aluminium for the ungrounded conductors, 8 AWG copper for the equipment grounding conductor.
- Neutral: it is a current-carrying conductor. Keep it the same size as the ungrounded conductors unless you have calculated that the unbalanced load allows a reduction.
- Dwelling service: a 100 A service to a dwelling unit may use the reduced service-conductor allowance in NEC 310.12, which is more generous than the ampacity table alone. That allowance is for dwelling units — it does not cover a subpanel feeding a workshop or a garage.
When 3 AWG copper is not enough
Voltage drop is what catches people out on 100 A feeders. Take 100 A over 40 m of 3 AWG copper: the conductor works out at roughly 0.026 Ω, so a single-phase 240 V circuit loses about 5.3 V — around 2.2%. Stretch the same run to 60 m and the drop reaches about 3.3%, past the usual 3% branch-circuit target, and 2 AWG becomes the right call.
The arithmetic is one line — drop = 2 × current × length × resistivity ÷ area, with the 2 accounting for the current travelling out and back — and the voltage drop calculator runs it with your own length, voltage and conductor material.
Metric sizing in practice
For a 100 A circuit on IEC-style installation, 25 mm² copper is the common starting point for a short, freely ventilated run, and 35 mm² is the usual choice once the run is long, the cable is grouped with others, or it is buried or in a thermally insulated wall. The current-carrying figure moves a long way between clipped direct, in conduit and inside insulation, so read it from the table for the method you actually have.
The breaker must match the cable
A 100 A breaker protects a cable rated at least 100 A after derating. A 100 A breaker on a conductor that can carry only 85 A is a fire waiting for a load — and a 100 A breaker on a conductor rated 125 A is simply a missed opportunity to protect the circuit properly.
Verify before you install
Ampacity tables, derating factors and the dwelling-service allowance live in the electrical code that applies where you work — NEC 2023 in the United States, with earlier editions still in force in some jurisdictions, and BS 7671 or IEC 60364 elsewhere. Treat the figures here as the starting point for that check rather than a substitute for it, and have installation work verified by a qualified professional.
Side-by-Side Worked Examples: North America (NEC) vs. International (IEC 60364 / BS 7671)
North American (NEC 2023/2026) Worked Example
Sizing a 100 A, 120/240 V feeder to a detached workshop subpanel 120 ft (36.6 m) away vs. a North America-specific dwelling service.
- Feeder vs. dwelling service rule: NEC 310.12 (North America dwelling unit services only) allows 4 AWG Cu / 2 AWG Al for a 100 A residential main service, but a detached workshop subpanel is a feeder governed by NFPA 70 Table 310.16 and NEC 110.14(C) 75 °C terminals — requiring 3 AWG Cu (100 A) or 1 AWG Al (100 A) with an 8 AWG Cu EGC.
- Voltage drop check at 80 A continuous subpanel load on 3 AWG Cu (26.67 mm²): ΔV = 2 × 80 × (0.0175 × 36.6 ÷ 26.67) = 3.84 V (1.60%) — well within 3%; verify Table 310.15(B)(1)(1) if ambient exceeds 30 °C.
International (IEC 60364 / BS 7671) Worked Example
Sizing a 100 A, 230 V 1-phase (or 400 V 3-phase) sub-main routed 35 m clipped direct (Method C) in 35 °C ambient beside one circuit (C_a = 0.94, C_g = 0.80, non-normative planning defaults; verify against IEC 60364-5-52 / BS 7671 Appendix 4 Table 4Ab).
- Coordination (I_b ≤ I_n ≤ I_z): Required base rating ≥ 100 ÷ (0.94 × 0.80) = 133.0 A -> select 35 mm² XLPE copper (typical Method C ~147 A -> I_z = 110.5 A, satisfying I_b ≤ I_n (100 A) ≤ I_z (110.5 A); un-derated 25 mm² would fail once grouped).
- Voltage drop & adiabatic PE: At 100 A single-phase, ΔV = 2 × 100 × (0.0175 × 35 ÷ 35) = 3.50 V (1.52%). For a 3,200 A earth fault cleared in 0.1 s (k = 143), adiabatic PE S = √(3,200² × 0.1) ÷ 143 = 7.08 mm² -> 10 mm² or 16 mm² protective conductor.
Related Calculators
Wire Size Calculator (Dual-Criteria Solver)
Size copper and aluminum conductors in AWG or mm² for ampacity and voltage drop.
Voltage Drop Calculator
Calculate AC and DC voltage drop across AWG or metric mm² copper and aluminum runs.
Circuit Breaker Size Calculator
Select circuit breaker and MCB ratings for continuous loads and cable ampacity.
Related Unit Converters
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Amps to Watts Converter
Convert current in amps (A) to active power in watts (W) for DC and AC systems.
AWG to mm² Converter (American Wire Gauge to Metric)
Convert American Wire Gauge (AWG) to metric mm² area, diameter, and resistance.
Frequently Asked Questions
Recommended Tools & Equipment for This Guide

Siemens Q2100 100-Amp Double-Pole Circuit Breaker
A 100-amp two-pole breaker for feeding a subpanel or a very large 240 V load.
- 100 amps per pole at 120/240 V — sized for subpanel feeders and very large 240 V loads.
- Common trip — both poles open together, as a feeder protection device must.
- Accepts 1 AWG through 4/0 conductors, torqued to 35 or 50 lb-in depending on the conductor size.

Fluke 325 True-RMS Clamp Meter
Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.
- AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
- Clamp-on measurement — read current without disconnecting or disturbing the circuit.
- Slim jaw profile — slides into crowded panels where bulky clamps will not fit.

Klein Tools CL800 Digital Clamp Meter
Wide-jaw auto-ranging clamp meter with inrush capture for motor and compressor starting currents.
- Inrush current capture — see the starting surge that trips breakers, not just the running current.
- Wide jaw opening — accepts larger conductors and bundled cables that slim clamps cannot.
- Auto-ranging true-RMS measurement — fast readings you can trust on non-linear loads.
Related Engineering Guides
Circuit Protection Basics: Breakers, Fuses, RCDs and Coordination
Coordinate miniature circuit breakers, fuses, and RCDs against faults and overloads.
How to Choose Cables & Wire
Select conductor sizes, insulation ratings, and cables for ampacity and drop limits.
How to Size a Circuit Breaker Correctly
Match breaker current ratings and trip curves to load demand and cable ampacity.