Skip to content
VoltCalcElectrical Calculators & Tools
Wiring Guides

How to Size a Circuit Breaker Correctly

VoltCalc EditorialPublished 2026-06-02Updated 2026-11-166 min read

Two constraints, one decision

A breaker must do two things at once: carry the normal load without nuisance tripping, and protect the cable from overload. That gives two constraints:

  1. Breaker rating ≥ load current (with margin for continuous loads)
  2. Breaker rating ≤ cable ampacity

The correct breaker is one that satisfies both.

Step one: find the load current

For a resistive load, current is power divided by voltage. For motors and other inductive loads, include power factor and efficiency. Use the Electrical Load Calculator if you are working from a connected load.

Step two: add margin

Continuous loads should not exceed about 80% of a breaker's rating, which is equivalent to sizing the breaker at 1.25× the load current. Then round up to the next standard rating — 6, 10, 16, 20, 25, 32 A and so on.

Step three: check the cable

Look up the cable's current-carrying capacity for its insulation type, installation method, ambient temperature and grouping. If the chosen breaker exceeds that figure, either use a larger cable or a smaller breaker.

Step four: consider the trip curve

  • Type B — general lighting and socket circuits with low inrush.
  • Type C — small motors and inductive loads with moderate inrush.
  • Type D — transformers and large motors with high inrush.

Why this matters

An oversized breaker lets a cable overheat before it trips — a fire risk. An undersized breaker trips constantly and tempts users to bypass it. Neither is acceptable.

The Circuit Breaker Size Calculator gives you the starting rating; always confirm against the cable's published capacity and your local code.

Side-by-Side Worked Examples: North America (NEC) vs. International (IEC 60364 / BS 7671)

North American (NEC 2023/2026) Worked Example

Size the breaker and conductor for a 240 V single-phase, 28 A continuous commercial HVAC heat strip running 75 ft (22.9 m) in copper THHN.

  1. Breaker sizing: Continuous factor = 28 × 1.25 = 35.0 A -> round up to a 40 A 2-pole breaker (standard NEC 240.6 rating).
  2. Conductor & terminal check: Select 8 AWG Cu (50 A at 75 °C; verify against NFPA 70 Table 310.16, Table 310.15(B)(1)(1) ambient/bundling, and NEC 110.14(C) 75 °C terminal limits). Voltage drop = 2 × 28 × (0.0175 × 22.9 ÷ 8.37) = 2.68 V (1.12%).
  3. Note on residential allowances: Dwelling service-entrance reductions (e.g., NEC 310.12 for 100 A/200 A main services) apply solely in North America and never to branch circuits.

International (IEC 60364 / BS 7671) Worked Example

Size an MCB and cable for a 230 V 1-phase, 26 A (I_b) commercial load installed clipped direct (Method C) for 35 m at 35 °C ambient beside two circuits (C_a = 0.94, C_g = 0.70, non-normative planning defaults; verify against IEC 60364-5-52 / BS 7671 Appendix 4 Table 4Ab).

  1. Coordination (I_b ≤ I_n ≤ I_z): Select standard breaker I_n = 32 A (Type B). Minimum un-derated cable capacity = 32 ÷ (0.94 × 0.70) = 48.6 A, so pick 10 mm² copper (~64 A Method C base -> derated I_z = 42.1 A would require 10 mm² XLPE at ~75 A base -> I_z = 49.4 A).
  2. Voltage drop & PE sizing: Drop = 2 × 26 × (0.0175 × 35 ÷ 10) = 3.19 V (1.39%). Adiabatic PE check at 1,500 A fault for 0.1 s (k = 143): S = √(1,500² × 0.1) ÷ 143 = 3.32 mm² -> 4 mm² CPC.

Related Calculators

Related Unit Converters

Frequently Asked Questions

Both must be satisfied. The breaker must carry the load but must not exceed the cable's current-carrying capacity.

Recommended Tools & Equipment for This Guide

Affiliate links — helps keep VoltCalc free
Siemens Q120 20-Amp Single-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q120 20-Amp Single-Pole Circuit Breaker

The standard 20-amp single-pole breaker for lighting, receptacles and small appliances on 120 V circuits.

Poles: 1 (single pole)Amperage: 20 AVoltage: 120 V AC
  • 20-amp single pole for 120 V circuits — sized for standard 12 AWG receptacle and lighting circuits.
  • 10 kA interrupting rating — handles the fault current available in typical residential panels.
  • SWD (switching duty) listed — approved for switching fluorescent lighting loads, not just overload protection.
Check Current Price
Siemens Q220 20-Amp Double-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q220 20-Amp Double-Pole Circuit Breaker

A 20-amp two-pole breaker for 240 V loads such as a small air conditioner, well pump or baseboard heater.

Poles: 2 (double pole, common trip)Amperage: 20 AVoltage: 120/240 V AC
  • 20 amps per pole at 120/240 V — supplies a 240 V load with a common-trip action.
  • Common trip — both poles open together, so a fault cannot leave one leg live.
  • 10 kA interrupting rating — appropriate for typical residential service fault levels.
Check Current Price
Siemens Q250 50-Amp Double-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q250 50-Amp Double-Pole Circuit Breaker

A 50-amp two-pole breaker for ranges, spa feeds, subpanels and 40-amp EV charging.

Poles: 2 (double pole, common trip)Amperage: 50 AVoltage: 120/240 V AC
  • 50 amps per pole at 120/240 V — ranges, spa circuits, subpanel feeds and 40 A EV charging.
  • Common trip — both poles open together on overload or fault.
  • 10 kA interrupting rating and HACR listing.
Check Current Price
Klein Tools ET310 Circuit Breaker Finder Kit
Klein ToolsNorth America (120V AC NEMA 5-15 GFCI)

Klein Tools ET310 Circuit Breaker Finder Kit

Finds the breaker feeding a circuit without shutting the panel down — the transmitter plugs into the outlet, the receiver traces it back.

Type: Circuit breaker finder kitIncluded: Receiver, transmitter, light socket adapter, ground adapter, carry caseWiring checks: Open ground, open neutral, open hot, hot/neutral reverse, hot/ground reverse
  • Transmitter and receiver pair — plug the transmitter into the socket, then sweep the receiver across the panel to identify the matching breaker.
  • Wiring status indicator on the transmitter — the same open ground, open neutral, open hot, reversed hot/neutral and reversed hot/ground checks as a standard outlet tester.
  • GFCI test button — trips a GFCI device to confirm it is actually protecting the circuit, not just installed.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →

Related Engineering Guides