Circuit Breaker Size Calculator
Calculate circuit breaker and MCB/MCCB ratings for NEC (125% continuous + 100% non-continuous or 100%-rated assembly) and IEC 60364 / BS 7671 (Ib ≤ In ≤ Iz, B/C/D trip curves, and Icn ≥ Ik).
Step-by-step calculation
- Active Context: NFPA 70 (NEC 2026) | Standard 80%-Rated Breaker (125% Cont.)
- Continuous Load Contribution = 32 A × 1.25 = 40.00 A
- Non-Continuous Load Contribution = 0 A × 1.00 = 0.00 A
- Minimum Required OCPD Rating = 40.00 A + 0.00 A = 40.00 A
- Next Standard NEC 240.6(A) Rating = 40 A
NEC 2023 & IEC 60364 reference. Check the result against NEC Table 310.16 or IEC 60364-5-52 at your termination temperature, and size the protective earthing / grounding conductor to the circuit rating.
Formula
Input definitions
| Symbol | Input | Unit | Meaning & code relevance |
|---|---|---|---|
| Std | Engineering Standard | — | Engineering input parameter for engineering standard, evaluated in real-time by the solver. |
| I_cont | Continuous Load Current (≥ 3 hrs) | A | Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity. |
| I_non | Non-Continuous Load Current (< 3 hrs) | A | Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity. |
| Assy | NEC Breaker Assembly Rating | — | Engineering input parameter for nec breaker assembly rating, evaluated in real-time by the solver. |
| AWG | NEC Protected Wire Check (NEC 240.4(D) Optional) | — | Engineering input parameter for nec protected wire check (nec 240.4(d) optional), evaluated in real-time by the solver. |
| I_k | Prospective Short-Circuit Current (Ik) | kA | Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity. |
| RCD | Residual Current / Earth Fault Protection | — | Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity. |
Worked example
Sizing a Breaker for 32 A Continuous + 5 A Non-Continuous Load
Compare NEC 210.20(A) sizing against IEC 60364-4-43 sizing.
- NEC Mode: I_min = (1.25 × 32 A) + (1.00 × 5 A) = 40 A + 5 A = 45 A → Select 45 A standard NEC 240.6(A) breaker.
- IEC Mode: Design current Ib = 32 + 5 = 37 A; IEC MCBs carry 100% continuous current without a 1.25× factor → Select 40 A Type C MCB (requiring cable Iz ≥ 40 A).
Assumptions
- In NEC mode, standard thermal-magnetic breakers are evaluated for 80% continuous loading (125% multiplier on loads running 3 hours or more per NEC 210.20(A) and 215.3) unless a listed 100%-rated assembly is selected.
- In IEC 60364 / BS 7671 mode, MCBs (EN 60898-1) and MCCBs (EN 60947-2) are rated for 100% continuous operation at reference ambient temperature, requiring Ib ≤ In ≤ Iz.
- Breaking capacity (AIC / Icn / Icu) is selected to equal or exceed the entered prospective short-circuit current Ik.
Limitations
- A circuit breaker must always be coordinated with the derated ampacity (Iz) of the conductor it protects.
- Motor branch-circuit short-circuit protection under NEC 430.52 (up to 250% FLA for inverse-time breakers) follows separate motor rules.
How it works
In NEC mode, applies 125% to continuous loads (or 100% for listed 100%-rated assemblies) plus 100% of non-continuous loads and selects the next standard NEC 240.6(A) breaker rating while checking NEC 240.4(D) small-conductor limits. In IEC / BS 7671 mode, applies Ib ≤ In ≤ Iz using 100%-rated IEC standard ratings, calculates instantaneous magnetic trip currents for Type B/C/D curves, and checks breaking capacity (Icn ≥ Ik).
When to use it
- Selecting the standard overcurrent breaker rating (MCB or MCCB) for mixed continuous and non-continuous loads under NEC 210.20(A) / 240.6(A) or IEC 60364-4-43.
- Verifying the fundamental IEC coordination inequality (I_b ≤ I_n ≤ I_z) so the breaker protects the derated cable ampacity without nuisance tripping.
- Choosing the appropriate MCB magnetic trip curve (Type B, Type C, or Type D) based on load inrush characteristics.
Practical real-world applications
- Commercial Lighting & EV Circuits: Sizing a 20 A or 40 A breaker for continuous loads that run for 3 hours or more using the 125% continuous duty rule (80% breaker loading).
- Distribution Board Coordination: Matching a 32 A Type C MCB to a grouped 6 mm² or 10 mm² cable after applying ambient and grouping derating factors.
- Inductive Equipment Protection: Selecting Type C or Type D trip curves for small transformers, HID lighting banks, and compressor circuits to prevent startup trips.
Original Editorial Review & Technical Evaluation
Sizes standard MCB and MCCB overcurrent protective device ratings (A) using NEC 125% continuous + 100% non-continuous duty rules or IEC 60364 Ib ≤ In ≤ Iz coordination.
Panelboard designers, residential/commercial electricians, and protection engineers coordinating breaker frames with cable ampacity.
- Enforces NEC 210.20(A)/215.3 (1.25× continuous + 1.0× non-continuous) rounded to NEC 240.6(A) standard frames
- Evaluates IEC 60364-4-43 Ib ≤ In ≤ Iz and selects B, C, or D trip curves plus RCD sensitivity guidance
- Checks NEC 240.4(D) small-conductor OCPD caps (#14 @ 15A, #12 @ 20A, #10 @ 30A) automatically
Accuracy & methodology: Applies steady-state thermal load multipliers and standard molded-case/miniature breaker step tables without modeling upstream-to-downstream time-current selectivity curves. High-inrush transformers or motors may require inverse-time curve verification with the manufacturer. Computational standards →
What to verify independently: Verify breaker interrupting rating (kA AIR / Icu) exceeds prospective fault current and confirm NEC 240.4(D), 240.6(A), or IEC 60898 / 60947-2 compliance.
Put the numbers to work with the Wire Size Calculator (Dual-Criteria Solver), Fuse Size Calculator and Earthing & Grounding Conductor Calculator (PE / CPC / EGC). For the background behind the numbers, read Circuit Protection Basics: Breakers, Fuses, RCDs and Coordination and How to Size a Circuit Breaker Correctly.
Common mistakes
- Applying the North American 1.25× continuous load multiplier to IEC MCBs (which are already 100% continuous-rated under EN 60898-1), causing unnecessary breaker and cable oversizing.
- Applying the 1.25× multiplier to non-continuous loads in NEC feeder and branch-circuit calculations.
- Selecting a Type B MCB on an inductive motor or transformer load where normal startup inrush exceeds 3–5× In, causing nuisance magnetic tripping.
Safety & code notice
Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.
Frequently asked questions
Related Calculators
Wire Size Calculator (Dual-Criteria Solver)
Size copper and aluminum conductors in AWG or mm² for ampacity and voltage drop.
Fuse Size Calculator
Select UL and IEC fuse ratings for general feeders and motor branch circuits.
Earthing & Grounding Conductor Calculator (PE / CPC / EGC)
Size protective earthing (PE / CPC) and equipment grounding conductors (EGC).
Short-Circuit Thermal Withstand & Fault Loop Calculator
Calculate cable short-circuit thermal withstand current and max clearing time.
Related Unit Converters
AWG to mm² Converter (American Wire Gauge to Metric)
Convert American Wire Gauge (AWG) to metric mm² area, diameter, and resistance.
mm² to AWG Converter (Metric Cable to American Wire Gauge)
Convert metric conductor area in mm² to the nearest AWG size and DC resistance.
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Electrical Length Converter (Meters, Feet, Inches, Yards, km, Miles)
Convert cable lengths between meters, feet, inches, millimeters, yards, and miles.
Related Engineering Guides
Recommended Wire Strippers, Crimpers & Circuit Protection Gear
Strip conductors without nicking strands, complete full-cycle ratcheting terminal crimps, tighten breaker and lug terminations to manufacturer pound-inch / N·m ratings with a calibrated torque screwdriver (NEC 110.14(D) / IEC 60947), and verify insulation resistance before energizing.

Siemens Q120 20-Amp Single-Pole Circuit Breaker
The standard 20-amp single-pole breaker for lighting, receptacles and small appliances on 120 V circuits.
- 20-amp single pole for 120 V circuits — sized for standard 12 AWG receptacle and lighting circuits.
- 10 kA interrupting rating — handles the fault current available in typical residential panels.
- SWD (switching duty) listed — approved for switching fluorescent lighting loads, not just overload protection.

Siemens QA120AFC 20-Amp Combination AFCI Breaker
A 20-amp AFCI breaker that detects arc faults as well as overloads — required on many dwelling branch circuits.
- Combination AFCI protection — detects series and parallel arc faults, not just overloads and short circuits.
- 20 amps, single pole, 120 V — fits a standard 20-amp branch circuit with 12 AWG conductors.
- 10 kA interrupting rating and HACR listing.

Klein Tools 11063W Wire Stripper and Cutter
Self-adjusting stripper that grips, strips and cuts common building wire in one motion.
- Self-adjusting action — squeeze once and the tool sets itself to the conductor size, so strips are repeatable.
- Clean strip without nicking — protects the copper, which is what keeps a termination reliable long term.
- Built-in cutter and plier nose — you can cut, strip and twist without swapping tools.

Klein Tools 3005CR Ratcheting Crimper
Ratcheting crimper that locks until the crimp is complete, so every termination is fully formed.
- Ratcheting mechanism — the tool stays locked until the crimp is fully formed, so a weak grip cannot produce a weak joint.
- 22–10 AWG range — covers the terminal sizes used in most panel and control wiring.
- Insulated and non-insulated terminals — one tool handles both, so you are not carrying two.