Circuit Breaker Size Calculator

Calculate circuit breaker and MCB/MCCB ratings for NEC (125% continuous + 100% non-continuous or 100%-rated assembly) and IEC 60364 / BS 7671 (Ib ≤ In ≤ Iz, B/C/D trip curves, and Icn ≥ Ik).

Recommended NEC Circuit Breaker Size
40 A
Verify against NFPA 70 (NEC) 210.20(A), 215.3, 240.4(D) small-conductor rules, and 240.6(A) standard ampere ratings.
I_min = (1.25 × I_continuous) + (1.00 × I_non-continuous) [NEC 210.20(A) / 215.3]
How we got here

Step-by-step calculation

  1. Active Context: NFPA 70 (NEC 2026) | Standard 80%-Rated Breaker (125% Cont.)
  2. Continuous Load Contribution = 32 A × 1.25 = 40.00 A
  3. Non-Continuous Load Contribution = 0 A × 1.00 = 0.00 A
  4. Minimum Required OCPD Rating = 40.00 A + 0.00 A = 40.00 A
  5. Next Standard NEC 240.6(A) Rating = 40 A
Minimum Calculated Rating40 A
Total Connected Current32 A
Continuous Load Factor125% (Standard 80% Breaker)
Max Continuous Load on Breaker32 A

NEC 2023 & IEC 60364 reference. Check the result against NEC Table 310.16 or IEC 60364-5-52 at your termination temperature, and size the protective earthing / grounding conductor to the circuit rating.

Formula

NEC: OCPD ≥ 1.25×I_cont + I_non | IEC: Ib ≤ In ≤ Iz

Input definitions

SymbolInputUnitMeaning & code relevance
StdEngineering Standard—Engineering input parameter for engineering standard, evaluated in real-time by the solver.
I_contContinuous Load Current (≥ 3 hrs)ASteady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.
I_nonNon-Continuous Load Current (< 3 hrs)ASteady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.
AssyNEC Breaker Assembly Rating—Engineering input parameter for nec breaker assembly rating, evaluated in real-time by the solver.
AWGNEC Protected Wire Check (NEC 240.4(D) Optional)—Engineering input parameter for nec protected wire check (nec 240.4(d) optional), evaluated in real-time by the solver.
I_kProspective Short-Circuit Current (Ik)kASteady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.
RCDResidual Current / Earth Fault Protection—Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity.

Worked example

Sizing a Breaker for 32 A Continuous + 5 A Non-Continuous Load

Compare NEC 210.20(A) sizing against IEC 60364-4-43 sizing.

  1. NEC Mode: I_min = (1.25 × 32 A) + (1.00 × 5 A) = 40 A + 5 A = 45 A → Select 45 A standard NEC 240.6(A) breaker.
  2. IEC Mode: Design current Ib = 32 + 5 = 37 A; IEC MCBs carry 100% continuous current without a 1.25× factor → Select 40 A Type C MCB (requiring cable Iz ≥ 40 A).
Result: 40 A

Assumptions

  • In NEC mode, standard thermal-magnetic breakers are evaluated for 80% continuous loading (125% multiplier on loads running 3 hours or more per NEC 210.20(A) and 215.3) unless a listed 100%-rated assembly is selected.
  • In IEC 60364 / BS 7671 mode, MCBs (EN 60898-1) and MCCBs (EN 60947-2) are rated for 100% continuous operation at reference ambient temperature, requiring Ib ≤ In ≤ Iz.
  • Breaking capacity (AIC / Icn / Icu) is selected to equal or exceed the entered prospective short-circuit current Ik.

Limitations

  • A circuit breaker must always be coordinated with the derated ampacity (Iz) of the conductor it protects.
  • Motor branch-circuit short-circuit protection under NEC 430.52 (up to 250% FLA for inverse-time breakers) follows separate motor rules.

How it works

In NEC mode, applies 125% to continuous loads (or 100% for listed 100%-rated assemblies) plus 100% of non-continuous loads and selects the next standard NEC 240.6(A) breaker rating while checking NEC 240.4(D) small-conductor limits. In IEC / BS 7671 mode, applies Ib ≤ In ≤ Iz using 100%-rated IEC standard ratings, calculates instantaneous magnetic trip currents for Type B/C/D curves, and checks breaking capacity (Icn ≥ Ik).

When to use it

  • Selecting the standard overcurrent breaker rating (MCB or MCCB) for mixed continuous and non-continuous loads under NEC 210.20(A) / 240.6(A) or IEC 60364-4-43.
  • Verifying the fundamental IEC coordination inequality (I_b ≤ I_n ≤ I_z) so the breaker protects the derated cable ampacity without nuisance tripping.
  • Choosing the appropriate MCB magnetic trip curve (Type B, Type C, or Type D) based on load inrush characteristics.

Practical real-world applications

  • Commercial Lighting & EV Circuits: Sizing a 20 A or 40 A breaker for continuous loads that run for 3 hours or more using the 125% continuous duty rule (80% breaker loading).
  • Distribution Board Coordination: Matching a 32 A Type C MCB to a grouped 6 mm² or 10 mm² cable after applying ambient and grouping derating factors.
  • Inductive Equipment Protection: Selecting Type C or Type D trip curves for small transformers, HID lighting banks, and compressor circuits to prevent startup trips.

Original Editorial Review & Technical Evaluation

Reviewed by VoltCalc Engineering Editorial

Sizes standard MCB and MCCB overcurrent protective device ratings (A) using NEC 125% continuous + 100% non-continuous duty rules or IEC 60364 Ib ≤ In ≤ Iz coordination.

Intended Users

Panelboard designers, residential/commercial electricians, and protection engineers coordinating breaker frames with cable ampacity.

Key Engineering Features
  • Enforces NEC 210.20(A)/215.3 (1.25× continuous + 1.0× non-continuous) rounded to NEC 240.6(A) standard frames
  • Evaluates IEC 60364-4-43 Ib ≤ In ≤ Iz and selects B, C, or D trip curves plus RCD sensitivity guidance
  • Checks NEC 240.4(D) small-conductor OCPD caps (#14 @ 15A, #12 @ 20A, #10 @ 30A) automatically

Accuracy & methodology: Applies steady-state thermal load multipliers and standard molded-case/miniature breaker step tables without modeling upstream-to-downstream time-current selectivity curves. High-inrush transformers or motors may require inverse-time curve verification with the manufacturer. Computational standards →

What to verify independently: Verify breaker interrupting rating (kA AIR / Icu) exceeds prospective fault current and confirm NEC 240.4(D), 240.6(A), or IEC 60898 / 60947-2 compliance.

Standards referenced:NFPA 70 (NEC 240.6(A))NEC 240.4(D)IEC 60364-4-43IEC 60898-1

Put the numbers to work with the Wire Size Calculator (Dual-Criteria Solver), Fuse Size Calculator and Earthing & Grounding Conductor Calculator (PE / CPC / EGC). For the background behind the numbers, read Circuit Protection Basics: Breakers, Fuses, RCDs and Coordination and How to Size a Circuit Breaker Correctly.

Common mistakes

  • Applying the North American 1.25× continuous load multiplier to IEC MCBs (which are already 100% continuous-rated under EN 60898-1), causing unnecessary breaker and cable oversizing.
  • Applying the 1.25× multiplier to non-continuous loads in NEC feeder and branch-circuit calculations.
  • Selecting a Type B MCB on an inductive motor or transformer load where normal startup inrush exceeds 3–5× In, causing nuisance magnetic tripping.

Safety & code notice

Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.

Frequently asked questions

Related Calculators

Related Unit Converters

Related Engineering Guides

Recommended Wire Strippers, Crimpers & Circuit Protection Gear

Affiliate links — helps keep VoltCalc free

Strip conductors without nicking strands, complete full-cycle ratcheting terminal crimps, tighten breaker and lug terminations to manufacturer pound-inch / N·m ratings with a calibrated torque screwdriver (NEC 110.14(D) / IEC 60947), and verify insulation resistance before energizing.

Siemens Q120 20-Amp Single-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q120 20-Amp Single-Pole Circuit Breaker

The standard 20-amp single-pole breaker for lighting, receptacles and small appliances on 120 V circuits.

Poles: 1 (single pole)Amperage: 20 AVoltage: 120 V AC
  • 20-amp single pole for 120 V circuits — sized for standard 12 AWG receptacle and lighting circuits.
  • 10 kA interrupting rating — handles the fault current available in typical residential panels.
  • SWD (switching duty) listed — approved for switching fluorescent lighting loads, not just overload protection.
Check Current Price
Siemens QA120AFC 20-Amp Combination AFCI Breaker
SiemensNorth America (120V/240V NEC UL 489 AFCI)

Siemens QA120AFC 20-Amp Combination AFCI Breaker

A 20-amp AFCI breaker that detects arc faults as well as overloads — required on many dwelling branch circuits.

Type: Combination-type AFCIPoles: 1 (single pole)Amperage: 20 A
  • Combination AFCI protection — detects series and parallel arc faults, not just overloads and short circuits.
  • 20 amps, single pole, 120 V — fits a standard 20-amp branch circuit with 12 AWG conductors.
  • 10 kA interrupting rating and HACR listing.
Check Current Price
Klein Tools 11063W Wire Stripper and Cutter
Klein ToolsGlobal / AWG Standard (8–20 AWG NEC & IEC)

Klein Tools 11063W Wire Stripper and Cutter

Self-adjusting stripper that grips, strips and cuts common building wire in one motion.

Type: Self-adjusting wire stripper / cutterCapacity: 8–18 AWG solid, 10–20 AWG strandedHandles: Dual-material, slip-resistant
  • Self-adjusting action — squeeze once and the tool sets itself to the conductor size, so strips are repeatable.
  • Clean strip without nicking — protects the copper, which is what keeps a termination reliable long term.
  • Built-in cutter and plier nose — you can cut, strip and twist without swapping tools.
Check Current Price
Klein Tools 3005CR Ratcheting Crimper
Klein ToolsGlobal / AWG Standard (10–22 AWG Terminals)

Klein Tools 3005CR Ratcheting Crimper

Ratcheting crimper that locks until the crimp is complete, so every termination is fully formed.

Type: Ratcheting crimping toolCapacity: 22–10 AWGTerminals: Insulated and non-insulated
  • Ratcheting mechanism — the tool stays locked until the crimp is fully formed, so a weak grip cannot produce a weak joint.
  • 22–10 AWG range — covers the terminal sizes used in most panel and control wiring.
  • Insulated and non-insulated terminals — one tool handles both, so you are not carrying two.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →