Electrical Formulas
A single-page engineering reference comparing DC, AC single-phase (1φ), and AC three-phase (3φ) electrical formulas side by side, with variable definitions and direct links to the matching calculators.
Dual-Annotated Electrical Formulas Matrix (NEC & IEC Symbols)
Direct mathematical relationships comparing DC, AC Single-Phase, and AC Three-Phase calculations with both North American (NEC) and International (IEC 60364 / BS 7671) notation.
| Parameter | NEC Symbol | IEC Symbol | Direct Current (DC) | AC Single-Phase (1φ) | AC Three-Phase (3φ) | Engineering Notes |
|---|---|---|---|---|---|---|
| Design / Load Current (Amperes) | I / FLA / FLC | Ib | I = V ÷ R | I = P ÷ V | Ib = P ÷ (U0 × cos φ) | I = P ÷ (V_L-N × PF) | Ib = P ÷ (√3 × U × cos φ) | I = P ÷ (√3 × V_L-L × PF) | Steady-state design current (Ib) or motor full-load current (FLA/FLC) through circuit conductors. |
| Voltage (Volts) | V_L-L / V_L-N | U / U0 | V = I × R | V = P ÷ I | U0 = P ÷ (Ib × cos φ) | V_L-N = P ÷ (I × PF) | U = P ÷ (√3 × Ib × cos φ) | V_L-L = P ÷ (√3 × I × PF) | Nominal system voltage: IEC line-to-line (U) / line-to-earth (U0) or NEC phase-to-phase (V_L-L) / phase-to-neutral (V_L-N). |
| Active Real Power (Watts) | P (W / kW) | P (W / kW) | P = V × I = I²R = V² ÷ R | P = U0 × Ib × cos φ | P = V_L-N × I × PF | P = √3 × U × Ib × cos φ | P = √3 × V_L-L × I × PF | Actual work performed or dissipated as thermal energy per second. |
| Apparent Power (Volt-Amps) | S (VA / kVA) | S (VA / kVA) | N/A (Identical to Watts) | S = U0 × Ib | S = V_L-N × I | S = √3 × U × Ib | S = √3 × V_L-L × I | Vector product of RMS voltage and RMS current used to rate transformers, UPS units, and switchgear. |
| Reactive Power (VAR) | Q (VAR / kVAR) | Q (var / kvar) | 0 VAR | Q = U0 × Ib × sin φ | Q = √3 × U × Ib × sin φ | Oscillating power sustained by electromagnetic/electrostatic fields in inductors and capacitors. |
| Horsepower & Motor Shaft Power | HP (1 hp = 745.7 W) | P_mech (kW / PS) | HP = (V × I × η) ÷ 745.7 | HP = (V × I × η × PF) ÷ 745.7 | HP = (√3 × V_L-L × I × η × PF) ÷ 745.7 | Mechanical shaft power converted to equivalent electrical input demand (1 mechanical hp = 745.7 W; 1 metric PS = 735.5 W). |
| Voltage Drop (Volts & ΔV%) | VD / %VD | ΔU / ΔV% | ΔV = 2 × I × R_eff × L | ΔV = 2 × Ib × (R cos φ + X sin φ) × L | ΔV = √3 × Ib × (R cos φ + X sin φ) × L | Potential lost along circuit conductors (ΔV% = 100 × ΔV ÷ V_source; planning limits: 3% branch / 5% total). |
| Overcurrent & Cable Coordination | OCPD ≥ 1.25 × I_cont | Ib ≤ In ≤ Iz | I_cont × 1.25 ≤ OCPD ≤ Iz | Ib ≤ In ≤ Iz & I2 ≤ 1.45 × Iz | Ib ≤ In ≤ Iz (Iz = It × Ca × Cg × Ci) | NEC 210.19/210.20 continuous load 125% rule vs. IEC 60364-4-43 overload coordination between design current (Ib), nominal device rating (In), and derated ampacity (Iz). |
| Adiabatic Protective Conductor Sizing (EGC / PE) | EGC (NEC 250.122) | PE / CPC (S = √(I²t) ÷ k) | S_min = √(I_f² × t) ÷ k | S_min = √(I_f² × t) ÷ k (Cu PVC k=115, XLPE k=143) | Zs ≤ U0 ÷ Ia (I_f = U0 ÷ Zs) | Minimum protective conductor cross-section (S in mm²) to withstand earth-fault energy I²t without exceeding insulation limit (IEC 60364-5-54 / BS 7671 Section 543). |
| Power Factor (PF / cos φ) | PF | cos φ / λ | 1.0 (Unity) | PF = P (kW) ÷ S (kVA) = cos φ | PF = P (kW) ÷ S (kVA) = cos φ | Ratio of real working power to total apparent power delivered by the source. |
Cross-Standard Symbol Reference: NFPA 70 (NEC) ↔ IEC 60364 / BS 7671
Side-by-side mapping of North American (FLA/FLC, OCPD, EGC, GFCI, V_L-L, V_L-N) and International (Ib, In, Iz, U, U0, PE/CPC, RCD, ΔV%, k, Zs) design symbols.
| Engineering Concept | NEC (NFPA 70) Term & Symbol | IEC 60364 / BS 7671 Term & Symbol | Key Formula / Coordination Rule |
|---|---|---|---|
| System Nominal Voltage | Line-to-Line / Line-to-Neutral Voltage V_L-L / V_L-N (e.g., 240/120 V, 480Y/277 V) | Nominal Line-to-Line / Line-to-Earth Voltage U / U0 (e.g., 400/230 V) | U = √3 × U0 in balanced 3-phase star/wye systems. |
| Circuit Design & Motor Current | Load Current / Full-Load Amps (Nameplate vs Table) I_load / FLA / FLC (NEC Table 430.250) | Design Current of Circuit Ib | NEC uses Table FLC for wire/breaker sizing and nameplate FLA for overload relays. |
| Protective Device & Cable Rating | Overcurrent Protective Device & Allowable Ampacity OCPD / Ampacity (NEC Table 310.16) | Nominal Device Current & Continuous Cable Rating In (MCB/Fuse) & Iz (IEC 60364-5-52) | IEC enforces Ib ≤ In ≤ Iz; NEC enforces OCPD ≥ 125% continuous load. |
| Protective Earthing / Grounding Conductor | Equipment Grounding Conductor EGC (NEC 250.122) | Protective Conductor / Circuit Protective Conductor PE / CPC (IEC 60364-5-54 / BS 7671 Table 54.7) | Provides low-impedance fault path so OCPD/RCD disconnects within allowable fault clearing time. |
| Shock & Earth-Leakage Protection | Ground-Fault Circuit Interrupter GFCI (5 mA Class A personnel protection) | Residual Current Device / RCBO RCD / RCCB / RCBO (IΔn = 30 mA additional protection) | Detects imbalance between live and neutral conductors caused by earth leakage. |
| Fault Loop & Thermal Withstand | Effective Ground-Fault Current Path I_sc / AIC (NEC 110.9 & 250.4) | Earth Fault Loop Impedance & Adiabatic Factor Zs (Ω) & k (A·s½/mm²) | Verifies automatic disconnection of supply (Zs ≤ U0 / Ia) within 0.4 s (final circuits) or 5 s (distribution). |
Related Calculators
Ohm's Law Calculator
Calculate voltage, current, resistance, and power in DC or resistive AC circuits.
Power Calculator
Calculate active, apparent, and reactive power from voltage, current, or PF.
Three Phase Power Calculator
Calculate real, apparent, and reactive power or line current in 3-phase systems.
Voltage Drop Calculator
Calculate AC and DC voltage drop across AWG or metric mm² copper and aluminum runs.
Related Unit Converters
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Amps to Watts Converter
Convert current in amps (A) to active power in watts (W) for DC and AC systems.
Volts to Watts Converter
Convert voltage (V) and current (A) into real power in watts for DC and AC loads.
kW to HP Converter (Kilowatts to Horsepower)
Convert kilowatts (kW) to mechanical (HP) and metric horsepower for motor sizing.
Related Engineering Guides
Ohm's Law Explained: Voltage, Current and Resistance
Master the relationship between voltage, current, resistance, and power in circuits.
Understanding Power Factor and Why It Matters
Understand real (kW), apparent (kVA), and reactive power (kVAR), and correct PF.
How to Calculate Voltage Drop in a Cable Run
Calculate 1-phase and 3-phase cable voltage drop and size wires within code limits.
Frequently Asked Questions
Related Equipment

Fluke 117 True-RMS Multimeter
The everyday electrician's meter: true-RMS AC measurement, non-contact voltage detection and a CAT III 600 V rating in a compact body.
- True-RMS AC measurement — accurate readings on the electronic loads that fool cheaper average-sensing meters.
- Built-in non-contact voltage detection — confirm a circuit is live before you put a probe anywhere near it.
- CAT III 600 V safety rating — rated for the transient energy you meet in distribution panels and fixed wiring.

Fluke 325 True-RMS Clamp Meter
Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.
- AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
- Clamp-on measurement — read current without disconnecting or disturbing the circuit.
- Slim jaw profile — slides into crowded panels where bulky clamps will not fit.

Klein Tools MM700 Auto-Ranging Multimeter
Auto-ranging true-RMS meter with a CAT IV 600 V rating and a tough, drop-tested housing.
- Auto-ranging — connect the probes and read the value, with no range dial to set first.
- True-RMS AC measurement — trustworthy numbers on drives, supplies and electronic lighting.
- CAT IV 600 V rating — the highest common safety category, covering outdoor and service-entrance work.