Electrical Formulas

A single-page engineering reference comparing DC, AC single-phase (1φ), and AC three-phase (3φ) electrical formulas side by side, with variable definitions and direct links to the matching calculators.

Dual-Annotated Electrical Formulas Matrix (NEC & IEC Symbols)

Direct mathematical relationships comparing DC, AC Single-Phase, and AC Three-Phase calculations with both North American (NEC) and International (IEC 60364 / BS 7671) notation.

ParameterNEC SymbolIEC SymbolDirect Current (DC)AC Single-Phase (1φ)AC Three-Phase (3φ)Engineering Notes
Design / Load Current (Amperes)I / FLA / FLCIbI = V ÷ R | I = P ÷ VIb = P ÷ (U0 × cos φ) | I = P ÷ (V_L-N × PF)Ib = P ÷ (√3 × U × cos φ) | I = P ÷ (√3 × V_L-L × PF)Steady-state design current (Ib) or motor full-load current (FLA/FLC) through circuit conductors.
Voltage (Volts)V_L-L / V_L-NU / U0V = I × R | V = P ÷ IU0 = P ÷ (Ib × cos φ) | V_L-N = P ÷ (I × PF)U = P ÷ (√3 × Ib × cos φ) | V_L-L = P ÷ (√3 × I × PF)Nominal system voltage: IEC line-to-line (U) / line-to-earth (U0) or NEC phase-to-phase (V_L-L) / phase-to-neutral (V_L-N).
Active Real Power (Watts)P (W / kW)P (W / kW)P = V × I = I²R = V² ÷ RP = U0 × Ib × cos φ | P = V_L-N × I × PFP = √3 × U × Ib × cos φ | P = √3 × V_L-L × I × PFActual work performed or dissipated as thermal energy per second.
Apparent Power (Volt-Amps)S (VA / kVA)S (VA / kVA)N/A (Identical to Watts)S = U0 × Ib | S = V_L-N × IS = √3 × U × Ib | S = √3 × V_L-L × IVector product of RMS voltage and RMS current used to rate transformers, UPS units, and switchgear.
Reactive Power (VAR)Q (VAR / kVAR)Q (var / kvar)0 VARQ = U0 × Ib × sin φQ = √3 × U × Ib × sin φOscillating power sustained by electromagnetic/electrostatic fields in inductors and capacitors.
Horsepower & Motor Shaft PowerHP (1 hp = 745.7 W)P_mech (kW / PS)HP = (V × I × η) ÷ 745.7HP = (V × I × η × PF) ÷ 745.7HP = (√3 × V_L-L × I × η × PF) ÷ 745.7Mechanical shaft power converted to equivalent electrical input demand (1 mechanical hp = 745.7 W; 1 metric PS = 735.5 W).
Voltage Drop (Volts & ΔV%)VD / %VDΔU / ΔV%ΔV = 2 × I × R_eff × LΔV = 2 × Ib × (R cos φ + X sin φ) × LΔV = √3 × Ib × (R cos φ + X sin φ) × LPotential lost along circuit conductors (ΔV% = 100 × ΔV ÷ V_source; planning limits: 3% branch / 5% total).
Overcurrent & Cable CoordinationOCPD ≥ 1.25 × I_contIb ≤ In ≤ IzI_cont × 1.25 ≤ OCPD ≤ IzIb ≤ In ≤ Iz & I2 ≤ 1.45 × IzIb ≤ In ≤ Iz (Iz = It × Ca × Cg × Ci)NEC 210.19/210.20 continuous load 125% rule vs. IEC 60364-4-43 overload coordination between design current (Ib), nominal device rating (In), and derated ampacity (Iz).
Adiabatic Protective Conductor Sizing (EGC / PE)EGC (NEC 250.122)PE / CPC (S = √(I²t) ÷ k)S_min = √(I_f² × t) ÷ kS_min = √(I_f² × t) ÷ k (Cu PVC k=115, XLPE k=143)Zs ≤ U0 ÷ Ia (I_f = U0 ÷ Zs)Minimum protective conductor cross-section (S in mm²) to withstand earth-fault energy I²t without exceeding insulation limit (IEC 60364-5-54 / BS 7671 Section 543).
Power Factor (PF / cos φ)PFcos φ / λ1.0 (Unity)PF = P (kW) ÷ S (kVA) = cos φPF = P (kW) ÷ S (kVA) = cos φRatio of real working power to total apparent power delivered by the source.

Cross-Standard Symbol Reference: NFPA 70 (NEC) ↔ IEC 60364 / BS 7671

Side-by-side mapping of North American (FLA/FLC, OCPD, EGC, GFCI, V_L-L, V_L-N) and International (Ib, In, Iz, U, U0, PE/CPC, RCD, ΔV%, k, Zs) design symbols.

Engineering ConceptNEC (NFPA 70) Term & SymbolIEC 60364 / BS 7671 Term & SymbolKey Formula / Coordination Rule
System Nominal Voltage
Line-to-Line / Line-to-Neutral Voltage
V_L-L / V_L-N (e.g., 240/120 V, 480Y/277 V)
Nominal Line-to-Line / Line-to-Earth Voltage
U / U0 (e.g., 400/230 V)
U = √3 × U0 in balanced 3-phase star/wye systems.
Circuit Design & Motor Current
Load Current / Full-Load Amps (Nameplate vs Table)
I_load / FLA / FLC (NEC Table 430.250)
Design Current of Circuit
Ib
NEC uses Table FLC for wire/breaker sizing and nameplate FLA for overload relays.
Protective Device & Cable Rating
Overcurrent Protective Device & Allowable Ampacity
OCPD / Ampacity (NEC Table 310.16)
Nominal Device Current & Continuous Cable Rating
In (MCB/Fuse) & Iz (IEC 60364-5-52)
IEC enforces Ib ≤ In ≤ Iz; NEC enforces OCPD ≥ 125% continuous load.
Protective Earthing / Grounding Conductor
Equipment Grounding Conductor
EGC (NEC 250.122)
Protective Conductor / Circuit Protective Conductor
PE / CPC (IEC 60364-5-54 / BS 7671 Table 54.7)
Provides low-impedance fault path so OCPD/RCD disconnects within allowable fault clearing time.
Shock & Earth-Leakage Protection
Ground-Fault Circuit Interrupter
GFCI (5 mA Class A personnel protection)
Residual Current Device / RCBO
RCD / RCCB / RCBO (IΔn = 30 mA additional protection)
Detects imbalance between live and neutral conductors caused by earth leakage.
Fault Loop & Thermal Withstand
Effective Ground-Fault Current Path
I_sc / AIC (NEC 110.9 & 250.4)
Earth Fault Loop Impedance & Adiabatic Factor
Zs (Ω) & k (A·s½/mm²)
Verifies automatic disconnection of supply (Zs ≤ U0 / Ia) within 0.4 s (final circuits) or 5 s (distribution).

Related Calculators

Related Unit Converters

Related Engineering Guides

Frequently Asked Questions

Almost every electrical calculation starts with Ohm's Law (V = I × R) and Watt's Law (P = V × I). By substituting one into the other, you get P = I²R and P = V²/R. For AC circuits, include power factor (PF = cos φ) and √3 (1.732) for balanced three-phase systems.

Related Equipment

Affiliate links — helps keep VoltCalc free
Fluke 117 True-RMS Multimeter
FlukeGlobal (CAT III 600V IEC 61010)

Fluke 117 True-RMS Multimeter

The everyday electrician's meter: true-RMS AC measurement, non-contact voltage detection and a CAT III 600 V rating in a compact body.

Type: True-RMS digital multimeterSafety rating: CAT III 600 VMeasures: Voltage, resistance, continuity, capacitance, frequency
  • True-RMS AC measurement — accurate readings on the electronic loads that fool cheaper average-sensing meters.
  • Built-in non-contact voltage detection — confirm a circuit is live before you put a probe anywhere near it.
  • CAT III 600 V safety rating — rated for the transient energy you meet in distribution panels and fixed wiring.
Check Current Price
Fluke 325 True-RMS Clamp Meter
FlukeGlobal (CAT III 600V / CAT IV 300V IEC 61010)

Fluke 325 True-RMS Clamp Meter

Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.

Type: True-RMS clamp meterCurrent: AC and DCSafety rating: CAT III 600 V
  • AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
  • Clamp-on measurement — read current without disconnecting or disturbing the circuit.
  • Slim jaw profile — slides into crowded panels where bulky clamps will not fit.
Check Current Price
Klein Tools MM700 Auto-Ranging Multimeter
Klein ToolsGlobal (CAT IV 600V IEC 61010)

Klein Tools MM700 Auto-Ranging Multimeter

Auto-ranging true-RMS meter with a CAT IV 600 V rating and a tough, drop-tested housing.

Type: Auto-ranging true-RMS digital multimeterSafety rating: CAT IV 600 VDisplay: Backlit LCD
  • Auto-ranging — connect the probes and read the value, with no range dial to set first.
  • True-RMS AC measurement — trustworthy numbers on drives, supplies and electronic lighting.
  • CAT IV 600 V rating — the highest common safety category, covering outdoor and service-entrance work.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →