Three Phase Power Calculator
Calculate real, apparent, and reactive power in a balanced three-phase system.
Step-by-step calculation
- Active Phase Configuration: Balanced 3-Phase AC (Line-to-Line V_L-L) | PF = 0.85
- S = √3 × 480 V × 50 A = 41569.2 VA
- P = 41569.2 VA × 0.85 = 35333.8 W
Formula
Input definitions
| Symbol | Input | Unit | Meaning & code relevance |
|---|---|---|---|
| V | System Voltage | V | Nominal RMS AC or steady-state DC system potential (e.g., 120V/240V/480V NEC or 230V/400V IEC 60038). |
| V_ref | Voltage Measurement Reference | — | Nominal RMS AC or steady-state DC system potential (e.g., 120V/240V/480V NEC or 230V/400V IEC 60038). |
| I_L | Line Current | A | Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity. |
| PF | Power Factor | — | Ratio of real power (kW) to apparent power (kVA), ranging from 0.01 to 1.00 for inductive/capacitive AC loads. |
Worked example
480V 3-Phase Distribution Feeder
50 A balanced load at 0.85 lagging power factor.
- P = 1.732 × 480 × 50 × 0.85 = 35.334 kW
- S = 1.732 × 480 × 50 = 41.569 kVA
Assumptions
- The three-phase load is balanced across all three phases (I_A = I_B = I_C).
- Entered voltage is selected as either RMS line-to-line voltage (V_L-L) or phase line-to-neutral voltage (V_L-N = V_L-L / √3).
- Waveforms are sinusoidal with a uniform displacement power factor across all phases.
Limitations
- Unbalanced three-phase systems with unequal phase currents must be calculated phase-by-phase using phase-to-neutral voltage (V_LN = V_LL ÷ √3) and summed.
- Neutral harmonic currents (such as triplen harmonics on 4-wire wye systems) are not modelled.
How it works
Uses √3 (1.732) line-to-line scaling (or 3 × V_L-N when Line-to-Neutral voltage is selected) for balanced wye or delta three-phase loads.
When to use it
- Calculating real power (kW), apparent power (kVA), reactive power (kVAR), or line current (I) in balanced 3-phase 3-wire and 4-wire AC systems.
- Converting between Line-to-Line voltage (V_LL, e.g., 400 V or 480 V) and Line-to-Neutral voltage (V_LN, e.g., 230 V or 277 V) in three-phase power formulas.
- Balancing feeder ampacity and switchgear bus loads across commercial and industrial distribution boards.
Practical real-world applications
- Calculating full-load line current for a 50 kW three-phase commercial kitchen or industrial oven bank on a 400 V (IEC) or 480 V (NEC) supply.
- Determining total kVA and kW load on a 208Y/120 V or 400Y/230 V main service switchboard from clamp-meter phase current measurements.
- Sizing 3-pole circuit breakers and feeder cables for three-phase HVAC rooftop units, air compressors, and elevator machine rooms.
Original Editorial Review & Technical Evaluation
Computes three-phase real power (kW), apparent power (kVA), reactive power (kVAR), and line current (A) using standard √3 line-to-line voltage relationships.
Industrial electrical engineers, commercial MEP designers, and plant electricians working on 208V, 400V, 415V, 480V, and 600V 3φ feeders.
- Supports Delta/Wye line-to-line RMS inputs (208V/480V NEC and 400V/415V IEC) with exact √3 geometry
- Solves P = √3 × V_L × I_L × PF alongside apparent S (kVA) and reactive Q (kVAR)
- Outputs equivalent phase-to-neutral Wye voltage (V_LN = V_LL ÷ √3) for panelboard load checks
Accuracy & methodology: Applies exact balanced three-phase symmetrical vector formulas assuming equal phase voltages separated by 120° and identical phase currents. Zero-sequence neutral current from unbalanced 1φ loads or triplen harmonics is not computed. Computational standards →
What to verify independently: Verify all three phase currents (L1, L2, L3) and neutral current in the field, and confirm NEC Article 220 / IEC 60364 demand factors.
Put the numbers to work with the VA Calculator, Power Factor Calculator and Motor Current Calculator. For the background behind the numbers, read Understanding Power Factor and Why It Matters and How to Choose a Clamp Meter.
Common mistakes
- Using Line-to-Neutral voltage (e.g., 230 V or 277 V) inside the √3 × V × I formula instead of Line-to-Line voltage (400 V or 480 V) — with V_LN you must multiply by 3, not √3.
- Forgetting the √3 (1.732) factor altogether and using the single-phase formula P = V × I × PF on a three-phase load (underestimating power by 42%).
- Assuming neutral current is zero on a 4-wire wye system feeding single-phase non-linear LED or IT loads, where 3rd-order triplen harmonics add constructively in the neutral.
Safety & code notice
Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.
Frequently asked questions
Related Calculators
VA Calculator
Calculate apparent power in VA and kVA for transformers, UPS units, and generators.
Power Factor Calculator
Calculate power factor, phase angle, real power (kW), kVA, and reactive kVAR.
Motor Current Calculator
Calculate full-load motor current, speed, starting inrush, and overload trip.
Transformer Calculator
Calculate 1-phase and 3-phase transformer kVA, full-load amps, and fault current.
Related Unit Converters
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Amps to Watts Converter
Convert current in amps (A) to active power in watts (W) for DC and AC systems.
Volts to Watts Converter
Convert voltage (V) and current (A) into real power in watts for DC and AC loads.
Related Engineering Guides
Recommended Clamp Meters & Diagnostic Tools for Power & Load Verification
Measure per-phase feeder current and line voltage with a CAT III/IV True-RMS clamp meter and trace branch circuit breakers before balancing panelboard loads.

Klein Tools CL800 Digital Clamp Meter
Wide-jaw auto-ranging clamp meter with inrush capture for motor and compressor starting currents.
- Inrush current capture — see the starting surge that trips breakers, not just the running current.
- Wide jaw opening — accepts larger conductors and bundled cables that slim clamps cannot.
- Auto-ranging true-RMS measurement — fast readings you can trust on non-linear loads.

Fluke 325 True-RMS Clamp Meter
Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.
- AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
- Clamp-on measurement — read current without disconnecting or disturbing the circuit.
- Slim jaw profile — slides into crowded panels where bulky clamps will not fit.

Fluke 1587 FC Insulation Multimeter
Insulation testing and full multimeter functions in one instrument, with selectable test voltages up to 1000 V.
- Insulation test voltages from 50 V to 1000 V — matches the test voltage to the equipment instead of using one fixed setting.
- Full true-RMS multimeter functions — voltage, current, resistance and continuity without a second instrument.
- Wireless result logging — builds a trend over time so you can see insulation degrading before it fails.

Fluke 117 True-RMS Multimeter
The everyday electrician's meter: true-RMS AC measurement, non-contact voltage detection and a CAT III 600 V rating in a compact body.
- True-RMS AC measurement — accurate readings on the electronic loads that fool cheaper average-sensing meters.
- Built-in non-contact voltage detection — confirm a circuit is live before you put a probe anywhere near it.
- CAT III 600 V safety rating — rated for the transient energy you meet in distribution panels and fixed wiring.