VA Calculator
Calculate apparent power in volt-amperes (VA) from voltage and current. Useful for sizing transformers, UPS systems, generators, and electrical equipment.
Step-by-step calculation
- VA = 120 V × 15 A
- VA = 1800 VA
- kVA = 1.8 kVA
Formula
Input definitions
| Symbol | Input | Unit | Meaning & code relevance |
|---|---|---|---|
| V | Voltage | V | Nominal RMS AC or steady-state DC system potential (e.g., 120V/240V/480V NEC or 230V/400V IEC 60038). |
| I | Current | A | Steady-state operating load current in amperes; compare with NEC Table 310.16 or IEC 60364-5-52 conductor ampacity. |
| φ | Phase | — | Electrical supply configuration: Single-Phase (2-wire) or balanced Three-Phase (3-wire/4-wire with √3 factor). |
Worked example
UPS Apparent Power Load
120 V circuit drawing 15 A.
- VA = 120 × 15 = 1800 VA (1.8 kVA)
Assumptions
- Voltage and current are taken as RMS values, which is how equipment ratings are quoted.
- Three-phase mode assumes a balanced load and a line-to-line voltage.
- The result is apparent power only — no allowance is made for power factor or for the equipment's own losses.
Limitations
- A VA figure sizes the capacity required, not the real power consumed. Convert with W = VA × PF to compare with a wattage rating.
- Motors and other inductive loads draw higher current at start-up than the steady value used here.
- Equipment is normally selected with headroom above the calculated figure; this tool does not pick a standard rating for you.
How it works
Apparent power (VA) represents total electrical capacity required from sources, transformers, and UPS systems regardless of load power factor.
When to use it
- Sizing Uninterruptible Power Supplies (UPS battery backups) in VA and kVA for servers, workstations, and networking racks.
- Determining required standby generator kVA capacity and distribution transformer kVA ratings for single-phase and three-phase loads.
- Calculating control-circuit transformer VA ratings for industrial contactor coils, solenoids, and PLC power supplies.
Practical real-world applications
- UPS Battery Backup Sizing: Converting a 900 W server rack load with a 0.75 power factor into 1,200 VA (and adding a 25% growth margin to select a 1,500 VA UPS).
- Generator & Transformer kVA Sizing: Calculating total apparent power demand (S = √3 × V_LL × I) on a 400 V or 480 V three-phase commercial feeder.
- Industrial Control Panel Design: Summing sealed and inrush VA of NEMA/IEC motor starter coils to size a 480V-to-120V control power transformer.
Original Editorial Review & Technical Evaluation
Calculates apparent power in volt-amperes (VA / kVA) and converts between real wattage (W / kW) and apparent capacity using circuit power factor.
Data center engineers sizing UPS and PDU capacity, control-panel designers selecting control transformers, and MEP specifiers.
- Calculates apparent power S = V × I (1φ/DC) and S = √3 × V_L × I_L (3φ balanced)
- Derives required VA directly from active Watts and load Power Factor (VA = W ÷ PF)
- Flags low-PF overhead so transformers and UPS systems are not thermally overloaded
Accuracy & methodology: Computes fundamental sinusoidal apparent power S = V_rms × I_rms assuming balanced phases and steady power factor. High-crest-factor IT/SMPS loads may demand additional VA headroom beyond displacement cos(θ). Computational standards →
What to verify independently: Verify continuous VA limits and derating for non-linear loads against UPS/transformer manufacturer datasheets and NEC Article 450 / IEC 60076.
Put the numbers to work with the Power Calculator, Power Factor Calculator and Three Phase Power Calculator. For the background behind the numbers, read Understanding Power Factor and Why It Matters and How to Choose an Inverter or UPS.
Common mistakes
- Sizing a UPS, inverter, or transformer in real Watts (W) equal to the load without dividing by Power Factor (VA = W ÷ PF), overloading the device’s current rating.
- Omitting the √3 (1.732) multiplier when calculating apparent power on a balanced three-phase circuit (S = √3 × V_LL × I).
- Confusing VA (apparent power) with VAR (reactive power) or assuming VA equals Watts on non-linear switch-mode power supplies.
Safety & code notice
Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.
Frequently asked questions
Related Calculators
Power Calculator
Calculate active, apparent, and reactive power from voltage, current, or PF.
Power Factor Calculator
Calculate power factor, phase angle, real power (kW), kVA, and reactive kVAR.
Three Phase Power Calculator
Calculate real, apparent, and reactive power or line current in 3-phase systems.
Transformer Calculator
Calculate 1-phase and 3-phase transformer kVA, full-load amps, and fault current.
Related Unit Converters
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Amps to Watts Converter
Convert current in amps (A) to active power in watts (W) for DC and AC systems.
Volts to Watts Converter
Convert voltage (V) and current (A) into real power in watts for DC and AC loads.
Related Engineering Guides
Recommended Clamp Meters & Diagnostic Tools for Power & Load Verification
Measure per-phase feeder current and line voltage with a CAT III/IV True-RMS clamp meter and trace branch circuit breakers before balancing panelboard loads.

Fluke 325 True-RMS Clamp Meter
Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.
- AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
- Clamp-on measurement — read current without disconnecting or disturbing the circuit.
- Slim jaw profile — slides into crowded panels where bulky clamps will not fit.

Klein Tools CL800 Digital Clamp Meter
Wide-jaw auto-ranging clamp meter with inrush capture for motor and compressor starting currents.
- Inrush current capture — see the starting surge that trips breakers, not just the running current.
- Wide jaw opening — accepts larger conductors and bundled cables that slim clamps cannot.
- Auto-ranging true-RMS measurement — fast readings you can trust on non-linear loads.

Fluke 117 True-RMS Multimeter
The everyday electrician's meter: true-RMS AC measurement, non-contact voltage detection and a CAT III 600 V rating in a compact body.
- True-RMS AC measurement — accurate readings on the electronic loads that fool cheaper average-sensing meters.
- Built-in non-contact voltage detection — confirm a circuit is live before you put a probe anywhere near it.
- CAT III 600 V safety rating — rated for the transient energy you meet in distribution panels and fixed wiring.

Siemens Q2100 100-Amp Double-Pole Circuit Breaker
A 100-amp two-pole breaker for feeding a subpanel or a very large 240 V load.
- 100 amps per pole at 120/240 V — sized for subpanel feeders and very large 240 V loads.
- Common trip — both poles open together, as a feeder protection device must.
- Accepts 1 AWG through 4/0 conductors, torqued to 35 or 50 lb-in depending on the conductor size.