200 Amp Wire Size: Gauge, Cable and Breaker

VoltCalc EditorialPublished 2026-11-05Updated 2026-11-168 min read

The short answer for 200 amps

Read straight off the 75 °C ampacity column, a 200 A circuit needs 3/0 AWG copper (200 A) or 250 kcmil aluminium (205 A). The equipment grounding conductor is 4 AWG copper or 2 AWG aluminium.

There is one important exception, and it is the reason you will see different numbers in different places: a 200 A service or feeder to a dwelling unit may use the reduced conductor allowance in NEC 310.12, which permits 2/0 AWG copper or 4/0 AWG aluminium. That allowance is specific to dwelling units.

Why 2/0 copper appears in so many answers

2/0 AWG copper carries 175 A at 75 °C, which is short of 200 A by the table — yet it is the conductor most 200 A house services actually use. The dwelling allowance exists because a residential service rarely carries its rating continuously, so the code permits service and feeder conductors sized to the service rating rather than to the full ampacity table.

Two consequences follow:

  • Do not carry the allowance across. A 200 A feeder to a workshop, a commercial unit or a detached outbuilding is not a dwelling service conductor, and needs 3/0 AWG copper or 250 kcmil aluminium.
  • Check the edition. The allowance has been renumbered and restated over successive code cycles. Confirm the clause in the edition in force where you build.

Reading the ampacity table properly

The number you may use depends on the weakest link in the chain:

  • Terminals. Equipment marked 75 °C lets you use the 75 °C column. Equipment marked 60 °C does not, no matter what the conductor insulation is rated.
  • Insulation. THHN, XHHW and their equivalents all carry temperature ratings, and each must be at least as high as the column you read.
  • Ambient. A feeder crossing a hot attic or running beside a boiler needs the ambient correction factor, and the derated value is what counts.
  • Grouping. Several current-carrying conductors in one raceway trigger an adjustment factor. A 200 A feeder is usually the only circuit in its conduit, but check before you assume it.

Voltage drop is the real constraint at 200 A

At 200 A, voltage drop decides the conductor far more often than ampacity does. On 3/0 copper the conductor sits at roughly 0.0083 Ω per 30 m, so a single-phase 240 V run of 30 m loses about 3.3 V — a little over 1.4%. At 60 m the same feeder loses about 2.8%, and at 80 m it passes 3.7% and needs 4/0.

That is why long service runs, garage subpanels and outbuilding feeders so often end up one or two sizes above the ampacity minimum. Run the numbers with the voltage drop calculator using your measured length — not an estimate — and remember that the round trip doubles the conductor length in the calculation.

Aluminium for big feeders

Above about 1/0, aluminium becomes the practical choice: lighter and cheaper at the sizes a 200 A feeder needs. The rules that keep it reliable are the same as for any aluminium conductor — terminals listed for the material, the torque on the label, and support that keeps the conductor from moving at the termination. Do not mix aluminium and copper under one terminal unless the connector is listed for both.

Breaker, panel and grounding

  • Breaker. A 200 A feeder is protected by a 200 A device. If the conductor is upsized for voltage drop, the breaker still matches the load and the panel rating, not the larger cable.
  • Panel. The feeder rating cannot exceed the busbar rating of the panel it lands on. A 200 A feeder on a 125 A panel is a mistake regardless of cable size.
  • Grounding. The equipment grounding conductor is sized to the overcurrent device — 4 AWG copper at 200 A. Where the ungrounded conductors are increased for voltage drop, the grounding conductor is increased in proportion.
  • Neutral. Same size as the ungrounded conductors unless a calculated unbalanced load permits a reduction, and never reduced on a service without checking the rule that applies.

Metric sizing

For a 200 A feeder in metric installation, 70 mm² to 95 mm² copper covers most real cases, with 95 mm² the common answer for conduit, grouping or a long run. As always, the current-carrying table for your installation method decides — the same conductor can be rated very differently clipped to a wall, in a duct, or inside thermal insulation.

Verify before you install

Conductor ampacities, dwelling allowances and grounding sizes come from the code in force where you work — NEC 2023 in the United States, with earlier editions in some jurisdictions, and BS 7671 or IEC 60364 elsewhere. Use the figures here as the starting point for that check, not a replacement for it, and have service and feeder work verified by a qualified professional.

Side-by-Side Worked Examples: North America (NEC) vs. International (IEC 60364 / BS 7671)

North American (NEC 2023/2026) Worked Example

Compare a 200 A, 120/240 V North American dwelling main service against a 200 A non-dwelling commercial feeder running 150 ft (45.7 m) at 75 °C terminations.

  1. Dwelling vs. commercial ampacity: Under NEC 310.12 (North America-specific residential rule), a 200 A single-family dwelling main service/feeder allows 2/0 AWG Cu or 4/0 AWG Al. For a commercial/outbuilding feeder where 310.12 does not apply, verify NFPA 70 Table 310.16 + NEC 110.14(C) 75 °C terminals, requiring 3/0 AWG Cu (85.0 mm²) or 250 kcmil Al (127 mm²) plus 4 AWG Cu EGC.
  2. Voltage drop check at 160 A load on 3/0 AWG Cu over 150 ft: ΔV = 2 × 160 × (0.0175 × 45.7 ÷ 85.0) = 3.01 V (1.25% of 240 V). At 250 kcmil Al (ρ_Al = 0.0282), ΔV = 2 × 160 × (0.0282 × 45.7 ÷ 127) = 3.25 V (1.35%); verify Table 310.15(B)(1)(1) for high ambient.

International (IEC 60364 / BS 7671) Worked Example

Size a 200 A, 400 V three-phase distribution sub-main running 45 m clipped direct (Method C) in 35 °C ambient beside one circuit (C_a = 0.94, C_g = 0.80, non-normative planning defaults; verify against IEC 60364-5-52 / BS 7671 Appendix 4 Table 4Ab).

  1. Coordination (I_b ≤ I_n ≤ I_z): Required tabulated ampacity ≥ 200 ÷ (0.94 × 0.80) = 266.0 A -> select 95 mm² XLPE copper (typical Method C ~282 A -> derated I_z = 212.1 A, satisfying I_b ≤ I_n (200 A) ≤ I_z (212.1 A)).
  2. 3-phase drop & adiabatic PE: ΔV = √3 × 200 × (0.0175 × 45 ÷ 95) = 2.87 V (0.72% of 400 V). For a 6,500 A fault cleared in 0.1 s (k = 143), adiabatic PE S = √(6,500² × 0.1) ÷ 143 = 14.37 mm² -> 16 mm² or 25 mm² PE conductor.

Related Calculators

Related Unit Converters

Frequently Asked Questions

At the 75 °C column, 3/0 AWG copper carries 200 A and 250 kcmil aluminium carries 205 A, so those are the plain ampacity answers. A 200 A service to a dwelling unit may use the reduced allowance in NEC 310.12, which permits 2/0 AWG copper or 4/0 AWG aluminium.

Recommended Tools & Equipment for This Guide

Affiliate links — helps keep VoltCalc free
Siemens Q2100 100-Amp Double-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q2100 100-Amp Double-Pole Circuit Breaker

A 100-amp two-pole breaker for feeding a subpanel or a very large 240 V load.

Poles: 2 (double pole, common trip)Amperage: 100 AVoltage: 120/240 V AC
  • 100 amps per pole at 120/240 V — sized for subpanel feeders and very large 240 V loads.
  • Common trip — both poles open together, as a feeder protection device must.
  • Accepts 1 AWG through 4/0 conductors, torqued to 35 or 50 lb-in depending on the conductor size.
Check Current Price
Fluke 325 True-RMS Clamp Meter
FlukeGlobal (CAT III 600V / CAT IV 300V IEC 61010)

Fluke 325 True-RMS Clamp Meter

Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.

Type: True-RMS clamp meterCurrent: AC and DCSafety rating: CAT III 600 V
  • AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
  • Clamp-on measurement — read current without disconnecting or disturbing the circuit.
  • Slim jaw profile — slides into crowded panels where bulky clamps will not fit.
Check Current Price
Fluke 1587 FC Insulation Multimeter
FlukeGlobal (CAT III 1000V / CAT IV 600V IEC 61010)

Fluke 1587 FC Insulation Multimeter

Insulation testing and full multimeter functions in one instrument, with selectable test voltages up to 1000 V.

Type: Insulation multimeterTest voltages: 50 / 100 / 250 / 500 / 1000 VSafety rating: CAT III 1000 V / CAT IV 600 V
  • Insulation test voltages from 50 V to 1000 V — matches the test voltage to the equipment instead of using one fixed setting.
  • Full true-RMS multimeter functions — voltage, current, resistance and continuity without a second instrument.
  • Wireless result logging — builds a trend over time so you can see insulation degrading before it fails.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →

Related Engineering Guides