200 Amp Wire Size: Gauge, Cable and Breaker
The short answer for 200 amps
Read straight off the 75 °C ampacity column, a 200 A circuit needs 3/0 AWG copper (200 A) or 250 kcmil aluminium (205 A). The equipment grounding conductor is 4 AWG copper or 2 AWG aluminium.
There is one important exception, and it is the reason you will see different numbers in different places: a 200 A service or feeder to a dwelling unit may use the reduced conductor allowance in NEC 310.12, which permits 2/0 AWG copper or 4/0 AWG aluminium. That allowance is specific to dwelling units.
Why 2/0 copper appears in so many answers
2/0 AWG copper carries 175 A at 75 °C, which is short of 200 A by the table — yet it is the conductor most 200 A house services actually use. The dwelling allowance exists because a residential service rarely carries its rating continuously, so the code permits service and feeder conductors sized to the service rating rather than to the full ampacity table.
Two consequences follow:
- Do not carry the allowance across. A 200 A feeder to a workshop, a commercial unit or a detached outbuilding is not a dwelling service conductor, and needs 3/0 AWG copper or 250 kcmil aluminium.
- Check the edition. The allowance has been renumbered and restated over successive code cycles. Confirm the clause in the edition in force where you build.
Reading the ampacity table properly
The number you may use depends on the weakest link in the chain:
- Terminals. Equipment marked 75 °C lets you use the 75 °C column. Equipment marked 60 °C does not, no matter what the conductor insulation is rated.
- Insulation. THHN, XHHW and their equivalents all carry temperature ratings, and each must be at least as high as the column you read.
- Ambient. A feeder crossing a hot attic or running beside a boiler needs the ambient correction factor, and the derated value is what counts.
- Grouping. Several current-carrying conductors in one raceway trigger an adjustment factor. A 200 A feeder is usually the only circuit in its conduit, but check before you assume it.
Voltage drop is the real constraint at 200 A
At 200 A, voltage drop decides the conductor far more often than ampacity does. On 3/0 copper the conductor sits at roughly 0.0083 Ω per 30 m, so a single-phase 240 V run of 30 m loses about 3.3 V — a little over 1.4%. At 60 m the same feeder loses about 2.8%, and at 80 m it passes 3.7% and needs 4/0.
That is why long service runs, garage subpanels and outbuilding feeders so often end up one or two sizes above the ampacity minimum. Run the numbers with the voltage drop calculator using your measured length — not an estimate — and remember that the round trip doubles the conductor length in the calculation.
Aluminium for big feeders
Above about 1/0, aluminium becomes the practical choice: lighter and cheaper at the sizes a 200 A feeder needs. The rules that keep it reliable are the same as for any aluminium conductor — terminals listed for the material, the torque on the label, and support that keeps the conductor from moving at the termination. Do not mix aluminium and copper under one terminal unless the connector is listed for both.
Breaker, panel and grounding
- Breaker. A 200 A feeder is protected by a 200 A device. If the conductor is upsized for voltage drop, the breaker still matches the load and the panel rating, not the larger cable.
- Panel. The feeder rating cannot exceed the busbar rating of the panel it lands on. A 200 A feeder on a 125 A panel is a mistake regardless of cable size.
- Grounding. The equipment grounding conductor is sized to the overcurrent device — 4 AWG copper at 200 A. Where the ungrounded conductors are increased for voltage drop, the grounding conductor is increased in proportion.
- Neutral. Same size as the ungrounded conductors unless a calculated unbalanced load permits a reduction, and never reduced on a service without checking the rule that applies.
Metric sizing
For a 200 A feeder in metric installation, 70 mm² to 95 mm² copper covers most real cases, with 95 mm² the common answer for conduit, grouping or a long run. As always, the current-carrying table for your installation method decides — the same conductor can be rated very differently clipped to a wall, in a duct, or inside thermal insulation.
Verify before you install
Conductor ampacities, dwelling allowances and grounding sizes come from the code in force where you work — NEC 2023 in the United States, with earlier editions in some jurisdictions, and BS 7671 or IEC 60364 elsewhere. Use the figures here as the starting point for that check, not a replacement for it, and have service and feeder work verified by a qualified professional.
Side-by-Side Worked Examples: North America (NEC) vs. International (IEC 60364 / BS 7671)
North American (NEC 2023/2026) Worked Example
Compare a 200 A, 120/240 V North American dwelling main service against a 200 A non-dwelling commercial feeder running 150 ft (45.7 m) at 75 °C terminations.
- Dwelling vs. commercial ampacity: Under NEC 310.12 (North America-specific residential rule), a 200 A single-family dwelling main service/feeder allows 2/0 AWG Cu or 4/0 AWG Al. For a commercial/outbuilding feeder where 310.12 does not apply, verify NFPA 70 Table 310.16 + NEC 110.14(C) 75 °C terminals, requiring 3/0 AWG Cu (85.0 mm²) or 250 kcmil Al (127 mm²) plus 4 AWG Cu EGC.
- Voltage drop check at 160 A load on 3/0 AWG Cu over 150 ft: ΔV = 2 × 160 × (0.0175 × 45.7 ÷ 85.0) = 3.01 V (1.25% of 240 V). At 250 kcmil Al (ρ_Al = 0.0282), ΔV = 2 × 160 × (0.0282 × 45.7 ÷ 127) = 3.25 V (1.35%); verify Table 310.15(B)(1)(1) for high ambient.
International (IEC 60364 / BS 7671) Worked Example
Size a 200 A, 400 V three-phase distribution sub-main running 45 m clipped direct (Method C) in 35 °C ambient beside one circuit (C_a = 0.94, C_g = 0.80, non-normative planning defaults; verify against IEC 60364-5-52 / BS 7671 Appendix 4 Table 4Ab).
- Coordination (I_b ≤ I_n ≤ I_z): Required tabulated ampacity ≥ 200 ÷ (0.94 × 0.80) = 266.0 A -> select 95 mm² XLPE copper (typical Method C ~282 A -> derated I_z = 212.1 A, satisfying I_b ≤ I_n (200 A) ≤ I_z (212.1 A)).
- 3-phase drop & adiabatic PE: ΔV = √3 × 200 × (0.0175 × 45 ÷ 95) = 2.87 V (0.72% of 400 V). For a 6,500 A fault cleared in 0.1 s (k = 143), adiabatic PE S = √(6,500² × 0.1) ÷ 143 = 14.37 mm² -> 16 mm² or 25 mm² PE conductor.
Related Calculators
Wire Size Calculator (Dual-Criteria Solver)
Size copper and aluminum conductors in AWG or mm² for ampacity and voltage drop.
Voltage Drop Calculator
Calculate AC and DC voltage drop across AWG or metric mm² copper and aluminum runs.
Circuit Breaker Size Calculator
Select circuit breaker and MCB ratings for continuous loads and cable ampacity.
Related Unit Converters
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Amps to Watts Converter
Convert current in amps (A) to active power in watts (W) for DC and AC systems.
AWG to mm² Converter (American Wire Gauge to Metric)
Convert American Wire Gauge (AWG) to metric mm² area, diameter, and resistance.
Frequently Asked Questions
Recommended Tools & Equipment for This Guide

Siemens Q2100 100-Amp Double-Pole Circuit Breaker
A 100-amp two-pole breaker for feeding a subpanel or a very large 240 V load.
- 100 amps per pole at 120/240 V — sized for subpanel feeders and very large 240 V loads.
- Common trip — both poles open together, as a feeder protection device must.
- Accepts 1 AWG through 4/0 conductors, torqued to 35 or 50 lb-in depending on the conductor size.

Fluke 325 True-RMS Clamp Meter
Clamp-on AC/DC current measurement in tight panels, with true-RMS accuracy and a CAT III 600 V rating.
- AC and DC current measurement — covers mains circuits, battery banks and solar strings with one tool.
- Clamp-on measurement — read current without disconnecting or disturbing the circuit.
- Slim jaw profile — slides into crowded panels where bulky clamps will not fit.

Fluke 1587 FC Insulation Multimeter
Insulation testing and full multimeter functions in one instrument, with selectable test voltages up to 1000 V.
- Insulation test voltages from 50 V to 1000 V — matches the test voltage to the equipment instead of using one fixed setting.
- Full true-RMS multimeter functions — voltage, current, resistance and continuity without a second instrument.
- Wireless result logging — builds a trend over time so you can see insulation degrading before it fails.
Related Engineering Guides
Circuit Protection Basics: Breakers, Fuses, RCDs and Coordination
Coordinate miniature circuit breakers, fuses, and RCDs against faults and overloads.
How to Choose Cables & Wire
Select conductor sizes, insulation ratings, and cables for ampacity and drop limits.
How to Size a Circuit Breaker Correctly
Match breaker current ratings and trip curves to load demand and cable ampacity.