Impedance Calculator
Calculate AC impedance from resistance and net reactance.
Step-by-step calculation
- Z = √(10² + 8²) = 12.8062 Ω
- Phase Angle θ = arctan(8 ÷ 10) = 38.66° (0.6747 rad)
- Power Factor cos θ = R ÷ Z = 0.7809 (Inductive / Lagging)
Formula
Input definitions
| Symbol | Input | Unit | Meaning & code relevance |
|---|---|---|---|
| R | Resistance | Ω | DC or equivalent AC ohmic resistance in ohms (Ω) at operating temperature. |
| X_L | Inductive Reactance | Ω | Engineering input parameter for inductive reactance measured in Ω, evaluated in real-time by the solver. |
| X_C | Capacitive Reactance | Ω | Engineering input parameter for capacitive reactance measured in Ω, evaluated in real-time by the solver. |
Worked example
Series RLC Circuit Impedance
R = 10 Ω, X_L = 12 Ω, X_C = 4 Ω.
- Net X = 12 − 4 = 8 Ω
- Z = √(10² + 8²) = √164 = 12.806 Ω
Assumptions
- Resistance (R), inductive reactance (X_L), and capacitive reactance (X_C) are connected in series at a single frequency.
- Inductive and capacitive reactances are 180° out of phase with each other and 90° out of phase with resistance.
- All circuit elements are linear and time-invariant.
Limitations
- Models series RLC combinations; parallel RLC tanks require admittance (1/Z) conversion.
- Reactance values X_L and X_C are valid only at the single frequency for which they were calculated.
How it works
Combines real resistance orthogonal to net reactance in the complex impedance plane via the Pythagorean theorem.
When to use it
- Combining series resistance (R) and net reactance (X) via vector addition (Z = √(R² + X²)) to find total AC circuit impedance and phase angle.
- Matching speaker and audio amplifier load impedances (4 Ω, 8 Ω, 16 Ω) and designing passive loudspeaker crossover networks.
- Evaluating AC filter networks, induction motor stator winding impedance, and feeder fault-loop impedance (Z_s = √(R² + X²)).
Practical real-world applications
- Speaker & Audio Load Matching: Calculating the complex impedance magnitude and phase shift of an 8 Ω woofer voice coil with series inductance at audio crossover frequencies.
- AC Filter & Snubber Design: Determining total impedance of an RC snubber or LC harmonic trap across industrial thyristor and relay contacts.
- Motor & Transformer Winding Analysis: Combining DC winding resistance R and leakage reactance X_L to find locked-rotor impedance and starting current.
Original Editorial Review & Technical Evaluation
Calculates total AC complex impedance magnitude |Z|, phase angle θ, and power factor (cos θ) for series RLC circuits.
Audio and RF network designers, protection engineers evaluating fault-path impedance, and electrical engineering students analyzing AC phasors.
- Computes vector impedance magnitude Z = √(R² + (X_L − X_C)²) and net reactance X_net
- Outputs phase angle θ in degrees (leading vs. lagging) and resulting displacement power factor
- Identifies inductive vs. capacitive dominance cleanly across any R, X_L, X_C combination
Accuracy & methodology: Uses lumped-element series phasor addition assuming steady-state single-frequency sinusoidal excitation. Distributed transmission-line reflections and frequency-dependent skin resistance are excluded. Computational standards →
What to verify independently: Cross-check complex loop impedance on power distribution circuits against measured fault-loop instruments and manufacturer cable R + jX tables.
Put the numbers to work with the Ohm's Law Calculator, Reactance Calculator and Power Factor Calculator. For the background behind the numbers, read Understanding Power Factor and Why It Matters and How to Choose Test & Measurement Equipment.
Common mistakes
- Adding resistance R and reactance X arithmetically (R + X) instead of taking the vector hypotenuse √(R² + X²), which overestimates impedance by up to 41%.
- Entering inductance in mH or capacitance in µF without converting to Henrys or Farads first when deriving reactance X for the impedance triangle.
- Using DC ohmmeter readings as the total AC impedance of a coil, solenoid, or speaker without accounting for frequency-dependent inductive reactance.
Safety & code notice
Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.
Frequently asked questions
Related Calculators
Ohm's Law Calculator
Calculate voltage, current, resistance, and power in DC or resistive AC circuits.
Reactance Calculator
Calculate inductive (XL) and capacitive (XC) reactance from frequency, L, or C.
Power Factor Calculator
Calculate power factor, phase angle, real power (kW), kVA, and reactive kVAR.
Three Phase Power Calculator
Calculate real, apparent, and reactive power or line current in 3-phase systems.
Related Unit Converters
Watts to Amps Converter
Convert active power in watts (W) to current in amps (A) for DC and AC circuits.
Amps to Watts Converter
Convert current in amps (A) to active power in watts (W) for DC and AC systems.
Volts to Watts Converter
Convert voltage (V) and current (A) into real power in watts for DC and AC loads.
Related Engineering Guides
Recommended Bench Multimeters & Soldering Equipment for Component Work
Verify component resistance and capacitance out-of-circuit with an auto-ranging True-RMS multimeter and use a temperature-controlled ESD-safe soldering station for clean joints.

Fluke 117 True-RMS Multimeter
The everyday electrician's meter: true-RMS AC measurement, non-contact voltage detection and a CAT III 600 V rating in a compact body.
- True-RMS AC measurement — accurate readings on the electronic loads that fool cheaper average-sensing meters.
- Built-in non-contact voltage detection — confirm a circuit is live before you put a probe anywhere near it.
- CAT III 600 V safety rating — rated for the transient energy you meet in distribution panels and fixed wiring.

AstroAI DM6000AR True-RMS Digital Multimeter
A true-RMS 6000-count meter with temperature, capacitance and a CAT III 600 V rating — the budget option for DIY, hobby and student work.
- True-RMS AC measurement — accurate readings on the distorted, non-sinusoidal waveforms that switch-mode supplies, dimmers and inverters produce, which is where average-sensing meters quietly mislead.
- 6000-count display with 0.1 mV and 0.1 µA resolution — more resolution on low-voltage and low-current work than a typical 2000-count budget meter, so small changes are visible rather than rounded away.
- CAT III 600 V and CAT II 1000 V safety rating — rated for the transient energy of distribution panels and fixed wiring, not just bench work.

Klein Tools MM700 Auto-Ranging Multimeter
Auto-ranging true-RMS meter with a CAT IV 600 V rating and a tough, drop-tested housing.
- Auto-ranging — connect the probes and read the value, with no range dial to set first.
- True-RMS AC measurement — trustworthy numbers on drives, supplies and electronic lighting.
- CAT IV 600 V rating — the highest common safety category, covering outdoor and service-entrance work.

Weller WE1010NA Digital Soldering Station
A 70 W temperature-controlled soldering station with a digital readout for consistent joints.
- 70 W element — recovers heat quickly on larger joints instead of stalling mid-solder.
- Digital temperature setpoint — repeatable settings job to job, rather than a vague dial position.
- Adjustable temperature range — works for fine electronics and heavier control wiring with one station.