Skip to content
VoltCalcElectrical Calculators & Tools

Motor Sizing Calculator

Size a motor from the driven load (kW or HP) or shaft torque: required rating, standard motor size, full-load and starting current (DOL/Y-Δ/VFD), and NEC Article 430 / IEC circuit sizing.

Selected Motor Rating
7.5 kW
The motor runs at 73.3% of its rating at the stated load. Starting current is typical for direct on line (dol) — confirm it against the motor nameplate and the manufacturer's data.
P_req = P_load × SF · I = P ÷ (√3 × V × PF × η)
How we got here

Step-by-step calculation

  1. Active Context: NFPA 70 (NEC 2026) | 3-Phase AC | 480 V | 1750 RPM
  2. P_load = 5.5 kW
  3. Required rating = 5.50 kW × 1.15 = 6.32 kW
  4. Next standard rating up = 7.5 kW (10.06 HP @ 745.7 W/HP)
  5. T = 9550 × 7.5 kW ÷ 1750 rpm = 40.93 Nm
  6. P_in = 7.5 kW ÷ 0.9 = 8.33 kW
  7. I_FLA = 7500 W ÷ (√3 × 480 V × 0.86 × 0.9) = 11.66 A
  8. I_start = 7 × 11.66 A = 81.59 A
Required Rating (Load × Service Factor)6.325 kW
Selected Rating10.0577 hp
Full-Load Current11.6552 A
Starting Current81.5862 A
Rated Torque40.9286 Nm
Input Power at Rated Load8.33333 kW
Load Factor73.3333 %
NEC 430.22 Min Conductor (125% FLC)17.5 A
NEC 430.52 Max Inverse Breaker (250% FLC)35 A

Formula

P_motor ≥ SF × P_load; T = 9550 × P ÷ RPM

Input definitions

SymbolInputUnitMeaning & code relevance
StdEngineering Standard—Engineering input parameter for engineering standard, evaluated in real-time by the solver.
UnitDriven Load Power Unit—Active electrical or mechanical power transfer (W/kW) dissipated or delivered to the load.
P_loadDriven Load PowerkW / HPActive electrical or mechanical power transfer (kW / HP) dissipated or delivered to the load.
RPMRated Shaft SpeedRPMUtility billing energy rate per kilowatt-hour (kWh) used to project operating electricity expenditure.
VSupply Voltage (3φ)VNominal RMS AC or steady-state DC system potential (e.g., 120V/240V/480V NEC or 230V/400V IEC 60038).
ηExpected Efficiency%Ratio of useful output power to total input power expressed as a percentage (η = P_out / P_in × 100).
StartStarting Method Multiplier—Engineering input parameter for starting method multiplier, evaluated in real-time by the solver.

Worked example

Sizing a Pump Motor for 5.5 kW Shaft Load

Determine IEC/NEMA frame power, FLA, locked-rotor inrush, and torque.

  1. Design margin 1.15 × 5.5 = 6.325 kW → 7.5 kW standard motor
  2. Torque = 9550 × 7.5 ÷ 1750 = 40.9 N·m
Result: 7.5 kW (10.1 HP)

Assumptions

  • A 1.15× design margin is applied to the continuous driven shaft power before selecting the next standard IEC/NEMA motor frame rating.
  • Rated full-load torque (N·m) is calculated at the entered shaft RPM using T = (9550 × kW) ÷ RPM.
  • Starting current is estimated from the selected starter type (7× DOL, 2.5× Star-Delta, 3× Soft Starter, 1.5× VFD).

Limitations

  • High-inertia loads (large fans, centrifuges, crushers) require checking accelerating torque and thermal stall time across the entire speed-torque curve.
  • High altitude (>1000 m) and ambient temperatures above 40°C require additional thermal derating.

How it works

Applies a 15% mechanical service margin, selects the next standard IEC/NEMA kW rating, and calculates 3-phase FLA, starter inrush, shaft torque, and NEC 430.22/430.52 branch sizing.

When to use it

  • Selecting the next standard NEMA Horsepower (HP) or IEC Kilowatt (kW) motor rating from required mechanical load power, duty factor, and service margin.
  • Sizing a complete motor branch circuit including 125% continuous conductor ampacity, thermal overload trip setting, and starter contactor rating.
  • Evaluating motor shaft torque (N·m and lb·ft) at 50 Hz or 60 Hz synchronous and full-load speeds.

Practical real-world applications

  • HVAC Blower & Industrial Pump Selection: Applying a 1.15–1.20 mechanical design margin to a 12 kW shaft load to select a standard 15 kW (IEC) or 20 HP (NEMA) motor frame.
  • Complete Branch-Circuit Schedule Generation: Producing required conductor ampacity, overload relay setting, and starter size for a new machine tool installation.
  • High-Altitude & Ambient Derating Planning: Upsizing motor frame capacity when installing air-cooled TEFC motors above 1,000 m (3,300 ft) elevation or in >40 °C boiler rooms.

Original Editorial Review & Technical Evaluation

Reviewed by VoltCalc Engineering Editorial

Sizes minimum required electric motor mechanical power (kW / HP) and output shaft torque (N·m / lb·ft) from driven load demand, drivetrain efficiency, and service factor.

Intended Users

Mechanical/MEP equipment designers, pump & fan specifiers, and conveyor engineers matching standard IEC/NEMA frame ratings.

Key Engineering Features
  • Accounts for mechanical transmission efficiency (gearboxes/belts) and duty service factor (SF)
  • Computes continuous shaft torque T = 9550 × P_kW ÷ RPM across 50 Hz and 60 Hz speeds
  • Maps calculated demand onto next larger standard NEMA HP and IEC kW motor frames

Accuracy & methodology: Sizes continuous running torque and mechanical power at nominal steady-state speed and ambient conditions. High-inertia breakaway torque, frequent start/stop thermal duty cycles (S1–S4), and high-altitude/high-ambient derating (> 40 °C or > 1,000 m) require additional margin. Computational standards →

What to verify independently: Check NEMA/IEC speed-torque curves against breakaway and pull-up load torque and apply altitude/ambient derating per NEMA MG 1 or IEC 60034-1.

Standards referenced:IEC 60034-1 (Duty S1)NEMA MG 1IEC 60072 (Frame Sizes)

Put the numbers to work with the Three Phase Power Calculator, Circuit Breaker Size Calculator and Motor Current Calculator. For the background behind the numbers, read Understanding Power Factor and Why It Matters and Circuit Protection Basics: Breakers, Fuses, RCDs and Coordination.

Common mistakes

  • Relying continuously on a motor’s 1.15 Service Factor (SF) for normal everyday load instead of selecting the next standard HP/kW frame size.
  • Sizing a motor for continuous running power without checking whether high-inertia loads (large fans, flywheels, loaded conveyors) exceed starting torque limits.
  • Operating a standard TEFC fan-cooled motor at low speed (e.g., 20 Hz) on a VFD under constant-torque load without an inverter-duty frame or auxiliary blower.

Safety & code notice

Calculator results are planning estimates. Always verify electrical designs against applicable local codes, standards (NEC / IEC), and consult a qualified professional.

Frequently asked questions

Related Calculators

Related Unit Converters

Related Engineering Guides

Recommended Inrush Clamp Meters & Insulation Testers for Motors & Transformers

Affiliate links — helps keep VoltCalc free

Capture locked-rotor starting inrush current with a True-RMS AC/DC clamp meter and trend winding-to-frame insulation resistance at 500 V / 1000 V DC before commissioning.

Klein Tools CL800 Digital Clamp Meter
Klein ToolsGlobal (CAT IV 600V IEC 61010)

Klein Tools CL800 Digital Clamp Meter

Wide-jaw auto-ranging clamp meter with inrush capture for motor and compressor starting currents.

Type: Auto-ranging true-RMS clamp meterSafety rating: CAT III 600 V / CAT IV 300 VSpecial function: Inrush current capture
  • Inrush current capture — see the starting surge that trips breakers, not just the running current.
  • Wide jaw opening — accepts larger conductors and bundled cables that slim clamps cannot.
  • Auto-ranging true-RMS measurement — fast readings you can trust on non-linear loads.
Check Current Price
Fluke 1587 FC Insulation Multimeter
FlukeGlobal (CAT III 1000V / CAT IV 600V IEC 61010)

Fluke 1587 FC Insulation Multimeter

Insulation testing and full multimeter functions in one instrument, with selectable test voltages up to 1000 V.

Type: Insulation multimeterTest voltages: 50 / 100 / 250 / 500 / 1000 VSafety rating: CAT III 1000 V / CAT IV 600 V
  • Insulation test voltages from 50 V to 1000 V — matches the test voltage to the equipment instead of using one fixed setting.
  • Full true-RMS multimeter functions — voltage, current, resistance and continuity without a second instrument.
  • Wireless result logging — builds a trend over time so you can see insulation degrading before it fails.
Check Current Price
Siemens Q240 40-Amp Double-Pole Circuit Breaker
SiemensNorth America (120V/240V NEC UL 489)

Siemens Q240 40-Amp Double-Pole Circuit Breaker

A 40-amp two-pole breaker for ranges, larger air conditioners and 32-amp EV charger circuits.

Poles: 2 (double pole, common trip)Amperage: 40 AVoltage: 120/240 V AC
  • 40 amps per pole at 120/240 V — suitable for ranges, large AC units and 32 A EV charging.
  • Common trip — both poles open together, so neither leg stays live after a fault.
  • 10 kA interrupting rating, HACR rated for air conditioning and refrigeration.
Check Current Price
Klein Tools 3005CR Ratcheting Crimper
Klein ToolsGlobal / AWG Standard (10–22 AWG Terminals)

Klein Tools 3005CR Ratcheting Crimper

Ratcheting crimper that locks until the crimp is complete, so every termination is fully formed.

Type: Ratcheting crimping toolCapacity: 22–10 AWGTerminals: Insulated and non-insulated
  • Ratcheting mechanism — the tool stays locked until the crimp is fully formed, so a weak grip cannot produce a weak joint.
  • 22–10 AWG range — covers the terminal sizes used in most panel and control wiring.
  • Insulated and non-insulated terminals — one tool handles both, so you are not carrying two.
Check Current Price
Affiliate Disclosure: VoltCalc may earn a commission from qualifying purchases made through product links at no extra cost to you. Product specs and availability are for reference and may change.Affiliate Disclosure →